RTU Open
15
4
Set the appropriate jumpers on the RTU Open.
J3
AO - 1
0 - 10 Vdc/4-20 mA
W1
Battery Jumper
In (Do not remove)
W2
Format Jumper*
Out
W3
Input 11 mA Jumper
Out (mA not utilized on this channel)
W4
Input 11 Thermistor
In (default position)
W5
Input 10 mA Jumper
Out (mA not utilized on this channel)
W6
Input 10 Thermistor Jumper
In (default position)
*Formatting the controller may result in lost information and should only be done under the guidance of
Carrier Control Systems Support.
Optional
*
Safety chain devices, field-installed - normally closed. Apply 24 Vac to this terminal
(jumper from
J1
- 1 to
J1
- 9) where no safety devices are installed.
**
Fire shutdown device, field-installed, configurable as normally open or closed
***
Enthalpy switch, field-installed - configurable as normally open or closed
- 42S (72 pages)
- 30GT (4 pages)
- 48SS060 (8 pages)
- 50ME (54 pages)
- 38AH024-034 (26 pages)
- ZC (28 pages)
- 30GA (12 pages)
- COMFORTLINK 48A2 (8 pages)
- 48HE003---006 (64 pages)
- 33ZCSECTRM (52 pages)
- 19XRV (40 pages)
- MODU-PAC 50DF (37 pages)
- 17DA (8 pages)
- SINGLE PACKAGED ELECTRIC COOLING UNITS 50GS (28 pages)
- 48JZ (N) 024-060 (30 pages)
- 30GX080-176 (8 pages)
- 50DL (24 pages)
- 50GL-A (4 pages)
- NP034-074 (72 pages)
- 40GXQ (12 pages)
- 30XA080-500 (8 pages)
- 39E (12 pages)
- 40KMQ------301 (10 pages)
- 38AE (12 pages)
- 48AW (118 pages)
- 38GXQ (28 pages)
- 48ES---A (38 pages)
- 48GL (22 pages)
- 48GH (22 pages)
- 40QA024-060 (24 pages)
- TJF004 (52 pages)
- 39LD (40 pages)
- 48DL (4 pages)
- 48/50TC04---28 (44 pages)
- 50EJ (56 pages)
- 17EX (120 pages)
- 50BB (8 pages)
- 50BA (24 pages)
- 50BB (16 pages)
- 50BJ (20 pages)
- 30H (16 pages)
- 48HJD005-007 (48 pages)
- 50ZP (6 pages)
- 50DP016 (16 pages)
- 50LJ008-014 (19 pages)