Wiring an occupancy switch or door contact, Wiring specifications – Carrier RTU OPEN 11-808-427-01 User Manual

Page 40

background image

Installation

34

RTU Open

To wire a compressor safety input to the controller

NOTES

An isolation relay may be required if the RTU Open is powered separately from the equipment's control

power circuit.

Follow device manufacturer's installation and operating instructions.


Wiring an occupancy switch or door contact

Occupancy switch - field-supplied
Door contact - field-supplied

Occupancy or door contact switches may be installed to provide an alternate means of occupancy

determination or heating and cooling lockout. See Sequence of Operation (page 43) for additional details.

Wiring specifications

Cable from sensor to controller:

If <100 ft (30.5 meters) 22 AWG, unshielded

If >100 ft (30.5 meters) 22 AWG, shielded

Maximum length:

500 feet (152 meters)