beautypg.com

Demand limiting, Door contact, Remote occupancy – Carrier RTU OPEN 11-808-427-01 User Manual

Page 56: Fire shutdown, Compressor safety

background image

Sequence of Operation

50

RTU Open

Demand Limiting

The RTU Open may employ a demand limit strategy. Demand limiting in the RTU Open works through setpoint

expansion. The controller’s heating and cooling setpoints are expanded in steps or levels. The degree to

which the setpoints are expanded is defined by the Demand Level Setpoints.
Each Demand Level (1 through 3) adjusts the heating and cooling setpoints outwards. By default, Demand 1

yields a 1° expansion, Demand 2 yields a 2° expansion, and Demand 3 yields a 4° expansion.
The BACnet Demand Limit variable sets the desired level of setpoint expansion in the receiving controller.

Level 0

leaves the standard occupied and unoccupied heating and cooling setpoints in effect. Levels 1

through 3 expands occupied heating and cooling setpoints.

Door contact

A Door Contact may be configured on any unused binary input. A typical application is an occupancy sensor

mounted within the space served by a single zone rooftop. Door Contact disables mechanical cooling and

electric or gas heating, when active. Economizer cooling, if available, continues to operate.

Remote occupancy

Remote occupancy

may be configured on any unused binary input channel. A typical application is a remote

contact, controlled by a third party, to set the controller's occupied mode. The Remote Occupancy function

requires both an input configured for Remote Occupancy, and Occupancy Source set to Remote Occ Input to

operate.
Once configured, the controller will operate in the occupied or unoccupied mode, as determined by the state

of the Remote Occupancy input.

Fire Shutdown

Fire Shutdown

may be configured on Binary Input 5. A typical application involves a smoke detector or fire

shutdown contact, which, when active, immediately shuts down equipment operation.

Compressor Safety

Compressor Safety

may be configured on Binary Input 3. A compressor safety tripped indicator circuit is

available on most Carrier rooftop equipment.
A Compressor Safety Alarm is shown on Properties page > Equipment tab > Alarms and indicates that the

equipment requires attention.
Cooling, heating, and supply fan outputs are not interrupted except where the RTU Open is configured for

Heat Pump operation. When configured for Heat Pump, and in the heating mode, a compressor safety fault

will cause the available stages of electric heating to be enabled in place of mechanical heating.
Normal operation resumes when the compressor safety circuit is de-energized.