Demand limiting, Door contact, Remote occupancy – Carrier RTU OPEN 11-808-427-01 User Manual
Page 56: Fire shutdown, Compressor safety
![background image](/manuals/69183/56/background.png)
Sequence of Operation
50
RTU Open
Demand Limiting
The RTU Open may employ a demand limit strategy. Demand limiting in the RTU Open works through setpoint
expansion. The controller’s heating and cooling setpoints are expanded in steps or levels. The degree to
which the setpoints are expanded is defined by the Demand Level Setpoints.
Each Demand Level (1 through 3) adjusts the heating and cooling setpoints outwards. By default, Demand 1
yields a 1° expansion, Demand 2 yields a 2° expansion, and Demand 3 yields a 4° expansion.
The BACnet Demand Limit variable sets the desired level of setpoint expansion in the receiving controller.
Level 0
leaves the standard occupied and unoccupied heating and cooling setpoints in effect. Levels 1
through 3 expands occupied heating and cooling setpoints.
Door contact
A Door Contact may be configured on any unused binary input. A typical application is an occupancy sensor
mounted within the space served by a single zone rooftop. Door Contact disables mechanical cooling and
electric or gas heating, when active. Economizer cooling, if available, continues to operate.
Remote occupancy
Remote occupancy
may be configured on any unused binary input channel. A typical application is a remote
contact, controlled by a third party, to set the controller's occupied mode. The Remote Occupancy function
requires both an input configured for Remote Occupancy, and Occupancy Source set to Remote Occ Input to
operate.
Once configured, the controller will operate in the occupied or unoccupied mode, as determined by the state
of the Remote Occupancy input.
Fire Shutdown
Fire Shutdown
may be configured on Binary Input 5. A typical application involves a smoke detector or fire
shutdown contact, which, when active, immediately shuts down equipment operation.
Compressor Safety
Compressor Safety
may be configured on Binary Input 3. A compressor safety tripped indicator circuit is
available on most Carrier rooftop equipment.
A Compressor Safety Alarm is shown on Properties page > Equipment tab > Alarms and indicates that the
equipment requires attention.
Cooling, heating, and supply fan outputs are not interrupted except where the RTU Open is configured for
Heat Pump operation. When configured for Heat Pump, and in the heating mode, a compressor safety fault
will cause the available stages of electric heating to be enabled in place of mechanical heating.
Normal operation resumes when the compressor safety circuit is de-energized.