beautypg.com

EVCO EPU2LXP1CH User Manual

Page 41

background image

EVCO S.p.A.

c-pro 3 micro and c-pro 3 kilo | Hardware manual ver. 1.0 | Code 114CP3UKE104

page 41 of 62

Networks /

UART1 (1)

Baud Rate

- - -

- - -

- - -

9600

Modbus communication baud rate in a

RS-485 network wired on the RS-485 port

with Modbus slave communication protocol

1200 =

1,200

baud

2400 =

2,400

baud

4800 =

4,800

baud

9600 =

9,600

baud

19200 = 19,200

baud

28800 = 28,000

baud

38400 = 38,400

baud

57600 = 57,600

baud

Networks /

UART1 (1)

Parity

- - -

- - -

- - -

EVEN

Modbus communication parity in a RS-485

network wired on the RS-485 port with

Modbus slave communication protocol

NONE = no

parity

ODD =

odd

EVEN = even

Networks /

UART1 (1)

Stop

- - -

- - -

- - -

1 BIT

Modbus communication stop bit number in a

RS-485 network wired on the RS-485 port

with Modbus slave communication protocol

1 BIT

= 1 bit

2 BIT

= 2 bit

Networks /

UART1 (1)

Timeout 2

240

s 10

Modbus communication time-out in a

RS-485 network wired on the RS-485 port

with Modbus slave communication protocol

for the test of the remote values of the I / O

(after this time without Modbus

communication, the request is considered

not sent and the controller moves to the

following request) (1)

Networks /

UART1 (1)

Address

1

247

- - -

1

local (or of the controller) Modbus node

address in a RS-485 network wired on the

RS-485 port with Modbus slave

communication protocol