7/36
8. MANUAL CYCLE
The manual cycle consists of the following three phases:
•
cooling
•
heating
•
climatization.
Each phase is independent and no automatic switch from a phase to another phase is available.
When the machine is in standby mode, press the MENU key and select the MANUAL menu by way of the INCREASE and
DECREASE keys, as follows:
Press ENTER to access the Manual Cycle setting mode. By way of the INCREASE and DECREASE keys, you can
switch from a phase to another. The cycle phase will be shown on the display, as follows:
Press ENTER to select a phase and the following setpoint will be shown on the display:
Press ENTER to access the change mode. The value in question will start blinking. Use the INCREASE and
DECREASE keys to change the value, as follows:
Press ENTER to confirm the setup value, which will stop blinking. You can now go to the humidity setpoint (if present)
and change it as follows:
Press ENTER to confirm. The number will stop blinking.
Press MENU to return to the phase selection and change the setpoint of the other phases.
Press START/STOP to run the selected phase; the display will show:
The first line shows that the heating phase of a manual cycle is being running and that it is 13:39.
The second line shows the temperature in the cell (5°C in this case), whether the use of the humidity probe is enabled and
the humidity percentage measured by the probe (63% in this case).
Press the MENU key to return to the display and set change, if any. By pressing the MENU key again you can view the
current phase. Use the START/STOP keys to start a new phase of the manual cycle.
Menu 01
Manual
Manual
Heating
Manuale
AirCon
Manual
Refrigeration
Heating
T=25°C
RH=80%
Manual
13:39
T= 5°C
%rH= 63%
Heating
T= 26°C
RH= 80%
Heating
T= 27°C
RG= 80%
Heating
T= 27°C
RH= 81%
Heating
T= 27°C
RH= 82%