Stop leavening specifications
CT1SA0040101
Vers. 1.11

21/36

Case 2

Setpoint+zm+ist

Setpoint

Sonda Umidità

Setpoint+zm

Setpoint

P44

P29

tempo

Elettrovalvola

Compressore

On

Off

Off

On

The solenoid valve is switched on for a period of time determined by parameter P44. If within this time the humidity

probe drops below the setpoint + dead zone value, if the setpoint + dead zone value is not reached within this time, the
solenoid valve will remain on and even the compressor will switch on until the setpoint + dead zone value is reached, then
the solenoid valve will go off and the compressor will remain on for the ‘on’ enforced time determined by parameter P29.


If the temperature in the cell is lower than parameter P31, dehumidification will be disabled.

If parameter P71 = 1 (output K3 does not manage the solenoid valve, only the light in the cell), dehumidification will

only require the compressor, which will be activated P44 seconds after the dehumidification request.