EVCO CT1SA0040101 User Manual
Page 31

Stop leavening specifications
CT1SA0040101
Vers. 1.11
31/36
P71
K3 management: 0 = solenoid valve; 1= light; 2 = dehumidification
0
2
1
--
P72
Compressor management with door open: 0 = no effect; 1 = switch off
compressor
0 1 0
--
P73
Defrost mode: 0 = resistances; 1 = hot gas
0
1
1
--
P74
Evaporator high temperature alarm
0
70
55
°C
P75
Enable evaporator high temperature alarm: 0 = not enabled; 1= enabled
0
1
1
--
P79
Maximum evaporator fans speed in heating
P57
100
100
%
P80
Maximum evaporator fans speed in air conditioning
P57 100 100
%
P81
Maximum evaporator fans speed in block
P57 100 100
%
P82
Maximum evaporator fans speed in preservation
P57 100 100
%
P83
Maximum evaporator fans speed in awaking
P57 100 100
%
P84
Maximum evaporator fans speed in rising
P57 100 100
%
P85
Maximum evaporator fans speed in slowing down
P57 100 100
%
P86
Maximum evaporator fans speed in cooling
P57 100 100
%
NOTE
•
Check the compressor protection time, as it is zero by default.
•
Parameters P5 and P6 are used to establish the humidity probe range. Parameter P5 must be equal to the
humidity percentage corresponding to 4mA and parameter P6 must be equal to the humidity percentage
corresponding to 20mA.
•
Check the automatic and manual program humidity setpoint after changing parameter P32