Stop leavening specifications
CT1SA0040101
Vers. 1.11

31/36

P71

K3 management: 0 = solenoid valve; 1= light; 2 = dehumidification

0

2

1

--

P72

Compressor management with door open: 0 = no effect; 1 = switch off
compressor

0 1 0

--

P73

Defrost mode: 0 = resistances; 1 = hot gas

0

1

1

--

P74

Evaporator high temperature alarm

0

70

55

°C

P75

Enable evaporator high temperature alarm: 0 = not enabled; 1= enabled

0

1

1

--

P79

Maximum evaporator fans speed in heating

P57

100

100

%

P80

Maximum evaporator fans speed in air conditioning

P57 100 100

%

P81

Maximum evaporator fans speed in block

P57 100 100

%

P82

Maximum evaporator fans speed in preservation

P57 100 100

%

P83

Maximum evaporator fans speed in awaking

P57 100 100

%

P84

Maximum evaporator fans speed in rising

P57 100 100

%

P85

Maximum evaporator fans speed in slowing down

P57 100 100

%

P86

Maximum evaporator fans speed in cooling

P57 100 100

%



NOTE

Check the compressor protection time, as it is zero by default.

Parameters P5 and P6 are used to establish the humidity probe range. Parameter P5 must be equal to the

humidity percentage corresponding to 4mA and parameter P6 must be equal to the humidity percentage
corresponding to 20mA.

Check the automatic and manual program humidity setpoint after changing parameter P32