TROUBLESHOOTING

7-9

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

SSOV FAULT

DURING PURGE

1. See SSOV SWITCH

OPEN

SSOV FAULT

DURING RUN

1. SSOV switch closed for

15 seconds during run.

1. Replace SSOV actuator.

SSOV RELAY

FAILURE

1. SSOV relay failed on

board.

1. Ensure that Neutral and Earth Ground are connected

at the source and there is no voltage measured

between them. Measurement should indicate near

zero or no more than a few millivolts.

2. Check the SSOV power wiring.
3. Press CLEAR button and restart unit. If fault persists,

replace Ignition/Stepper (IGST) Board.

SSOV

SWITCH OPEN

1. Actuator not allowing for

full closure of gas valve

2. SSOV powered when it

should not be

3. Defective Switch or

Actuator

4. Incorrectly wired switch.

1. Observe operation of the Safety Shut-Off Valve

(SSOV) through indicator on the Valve actuator and

ensure that the valve is fully and not partially closing.

2. If the SSOV never closes, it may be powered

continuously. Close the gas supply and remove

power from the unit. Refer fault to qualified service

personnel.

3. Remove the electrical cover from the SSOV and

check switch continuity. If the switch does not show

continuity with the gas valve closed, either adjust or

replace the switch or actuator.

4. Ensure that the SSOV Proof of Closure switch is

correctly wired.

STEPPER MOTOR

FAILURE

1. Air/Fuel Valve out of

calibration.

2. Air/Fuel Valve

unplugged.

3. Loose wiring connection

to the stepper motor.

4. Defective Air/Fuel Valve

stepper motor.

5. Defective Power Supply

Board or fuse

6. Defective IGST Board

1. Refer to GF-112 and perform Stepper Test (para.

6.3.5) to ensure stepper motor rotates properly

between the 0% (fully closed) and 100% (fully open)

positions. Verify that the FIRE RATE bargraph and

the dial on the Air/Fuel Valve track each other to

indicate proper operation. If operation is not correct,

perform the Stepper Feedback Calibration (GF-112,

para. 6.2.1).

2. Check to ensure that the Air/Fuel Valve is connected

to the Control Box.

3. .Inspect for loose connections between the Air/Fuel

Valve motor and the wiring harness.

4. Replace stepper motor.

5. Check DS1 & DS2 LEDs on Power Supply Board. If

they are not steady ON, replace Power Supply Board.

6. Check “Heartbeat” LED DS1 and verify it is blinking

ON & OFF every second. If not, replace IGST Board.