beautypg.com

Troubleshooting – AERCO KC Series Equipped with C-More Controller for Massachusetts Only User Manual

Page 67

background image

TROUBLESHOOTING

7-4

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

FFWD TEMP

SENSOR FAULT

1. Loose or broken wiring.

2. Defective Sensor.

3. Incorrect Sensor.

1. Inspect feed forward (BTU transmitter) sensor

for loose or broken wiring.

2. Check resistance of sensor to determine if it is

within specification.

3. Ensure that the correct sensor is installed.

FLAME LOSS

DURING RUN

1. Worn Flame Detector

or cracked ceramic.

2. Defective Differential

Regulator.

3. Poor combustion

calibration.

4. Debris on burner.

5. Blocked condensate

drain.

1. Remove and inspect the Flame Detector for

signs of wear or cracked ceramic. Replace if

necessary.

2. Check gas pressure readings using a gauge or

manometer into and out of the Air/Fuel Valve to

ensure that the gas pressure into and out of the

valve is correct.

3. Check combustion calibration. Adjust as

necessary.

4. Remove the burner and inspect for any carbon

or debris. Clean and reinstall.

5. Remove blockage from condensate drain.

HEAT DEMAND

FAILURE

1. The Heat Demand

Relays on the

Ignition/Stepper (IGST)

board failed to activate

when commanded

2. Relay is activated when

not in Demand

1. Press CLEAR button and restart the unit. If the

fault persists, replace IGST Board.

2. Defective relay. Replace IGST Board.

HIGH EXHAUST

TEMPERATURE

1. Defective exhaust

sensor.

2. Carboned heat

exchanger due to

incorrect combustion

calibration

1. Measure the actual exhaust temperature and

continuity of the exhaust sensor. If the exhaust

temperature is less than 500

o

F and the

exhaust sensor shows continuity replace the

sensor.

2. If exhaust temperature is greater than 500

o

F,

check combustion calibration. Calibrate or

repair as necessary.

HIGH GAS

PRESSURE

1. Incorrect supply gas

pressure.

2. Defective Supply

Regulator or Wrong

Style Regulator

1. If using a non-lock up style regulator for the gas

supply, measure static gas pressure

downstream, it should be 14”WC or less. Adjust

as necessary.

2. If gas supply pressure cannot be lowered, a

lock-up style regulator may be required or the

supply regulator may be defective.