beautypg.com

Troubleshooting – AERCO KC Series Equipped with C-More Controller for Massachusetts Only User Manual

Page 65

background image

TROUBLESHOOTING

7-2

KC1000 WATER HEATER TROUBLESHOOTING TABLE

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

AIRFLOW FAULT

DURING IGNITION

1. Blower stopped running

due to thermal or current

overload

2. Blocked Blower inlet or

inlet ductwork

3. Blocked airflow switch

4. Defective airflow switch

1. Check combustion blower for signs of excessive

heat or high current drain that may trip thermal or

current overload devices.

2. Inspect the inlet to the combustion blower

including any duct work leading up to the

combustion blower for signs of blockage.

3. Remove the airflow switch and inspect for signs

of blockage, clean or replace as necessary.

4. Measure the airflow switch for continuity with the

combustion blower running. If there is an erratic

resistance reading or the resistance reading is

greater than zero ohms, replace switch.

AIRFLOW FAULT

DURING PURGE

1. Blower not running

2. Defective Air Flow Switch

3. Blocked Air flow Switch

4. Blocked Blower inlet or

inlet ductwork.

5. No voltage to switch from

control box.

1. Start the unit. If the blower does not run check the

blower solid state relay for input and output

voltage. If the relay is okay, check the blower.

2. Start the unit. If the blower runs, check the airflow

switch for continuity. Replace the switch if there is

no continuity.

3. Remove the air flow switch and inspect for signs of

blockage, clean or replace as necessary.

4. Inspect the inlet to the combustion blower

including any ductwork leading up to the

combustion blower for signs of blockage.

5. Measure for 24 VAC during start sequence from

each side of the switch to ground. If 24VAC is not

present refer to qualified service personnel.

AIRFLOW FAULT

DURING RUN

1. Blower stopped running

due to thermal or current

overload

2. Blocked Blower inlet or

inlet ductwork

3. Blocked airflow switch

4. Defective airflow switch

5. Combustion oscillations

1. Check combustion blower for signs of excessive

heat or high current draw that may trip thermal or

current overload devices.

2. Inspect the inlet to the combustion blower

including any ductwork leading up to the

combustion blower for signs of blockage.

3. Remove the airflow switch and inspect for signs of

blockage, clean or replace as necessary.

4. Measure the airflow switch for continuity with the

combustion blower running. If there is an erratic

resistance reading or the resistance reading is

greater than zero ohms, replace the switch.

5. Run unit to full fire. If the unit rumbles or runs

rough, perform combustion calibration.