Figure 2.3, Inlet and outlet location, Installation – AERCO KC Series Equipped with C-More Controller for Massachusetts Only User Manual

Page 13

background image

INSTALLATION

2-3

Shut-off valves and union conections must be

installed in the inlet and outlet lines for main-

tenance. The use of dielectric unions is recom-

mended. Install the piping and accessories as

per the following drawings, located in Appendix F

of this manual.

SD-A-424 for single units

SD-A-425 for multiple units

SD-A-432 for single units with a stratified

tank

SD-A-434 for multiple units with a stratified

storage tank

NOTE:

All piping must be arranged so that it does

not interfere with removal of any cover,

inhibit service or maintenance, or prevent

access between the unit and walls, or

another unit.

Figure 2.3

Inlet and Outlet Location

2.3.3 TEST HOSE BIB

A Test Hose Bib connection, upstream of the

shut off valve on the hot water outlet, is required

for startup and testing. It should be a minimum

of 3/4".

It cannot be omitted (See Fig. 2.4a)

Figure 2.4a

Hose Bib Location

2.3.4 PRESSURE/TEMPERATURE

RELIEF AND DRAIN

VALVE

INSTALLATION

An ASME rated Pressure/Temperature Relief

Valve is supplied with each unit. The valve

setpoint is 150 psig/210

°

F. Install the relief valve

as shown in Fig. 2.4b. A suitable pipe compound

should be used on the threaded connections.

Any excess should be wiped off to avoid getting

any into the valve body. The relief valve should

be piped to within 12 inches of the floor to

prevent injury in the event of a discharge. The

relief piping must be full size, 1-1/2”, without

reduction. No valves, restrictions, or other

blockages are allowed in the discharge line. In

multiple unit installations the discharge lines

must not

be manifolded together. Each must be

individually run to a suitable discharge location.

A 1” drain valve assembly is furnished with each

unit. The assembly should be installed as shown

in Figure 2.4b. The drain should be hard piped to

a suitable drain.

2.3.5 SYSTEM RECIRCULATION

The system recirculating line ties into the unit at

the recirculating tee fitting provided in the drain

valve assembly (see Fig. 2.4b). Shut off valves

and union connections are recommended for

maintenance. Recirculation flow rates must be

kept to 8 gpm or less. In a multiple unit

installation, each unit must be tied into the

system recirculation system.