beautypg.com

Troubleshooting – AERCO KC Series Equipped with C-More Controller for Massachusetts Only User Manual

Page 71

background image

TROUBLESHOOTING

7-8

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

(continued)

3. Switch wired incorrectly.

4. Defective Power Supply

Board or fuse

5. Defective IGST Board

3. If the switch is wired correctly, replace the

switch.

4. Check DS1 & DS2 LEDs on Power Supply

Board. If they are not steady ON, replace

Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is

blinking ON & OFF every second. If not,

replace IGST Board.

PRG SWTCH OPEN

DURING PURGE

1. Defective purge switch.

2. No voltage present at

switch.

3. Switch wired incorrectly.

4. Defective Power Supply

Board or fuse

5. Defective IGST Board

1. If the air-fuel valve does rotate, check the

purge switch for continuity when closing.

Replace switch if continuity does not exist.

2. Measure for 24 VAC from each side of the

switch to ground. If 24VAC is not present,

refer fault to qualified service personnel.

3. Check to ensure that the switch is wired

correctly (correct wire numbers on the

normally open terminals).

4. Check DS1 & DS2 LEDs on Power Supply

Board. If they are not steady ON, replace

Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is

blinking ON & OFF every second. If not,

replace IGST Board.

REMOTE SETPT

SIGNAL FAULT

1. Remote setpoint signal not

present:

Not yet installed.

Wrong polarity.

Signal defective at source.

Broken or loose wiring.

2. Signal is not isolated

(floating) if 4 to 20 mA.

3. Control Box signal type

selection switches not set

for correct signal type

(voltage or current).

1. Check I/O Box to ensure signal is hooked up.

Hook up if not installed.

If installed, check polarity.

Measure signal level.

Check continuity of wiring between source and

boiler.

2. Check signal at source to ensure it is isolated.

3. Check DIP switch on PMC board to ensure it

is set correctly for the type of signal being

sent. Check control signal type set in

Configuration Menu.

RESIDUAL

FLAME

1. SSOV not fully closed.

2. Defective Flame Detector.

1. Check open/close indicator window of Safety

Shut-Off Valve (SSOV) and ensure that the

SSOV is fully closed. If not fully closed,

replace the valve and or actuator.

Close gas shut-off valve downstream of

SSOV. Install a manometer or gauge in a gas

test port between the SSOV and the gas shut

off valve. If a gas pressure reading is

observed replace the SSOV valve and or

actuator.

2. Replace Flame Detector.