Control panel operating procedures – AERCO KC Series Equipped with C-More Controller for Massachusetts Only User Manual

Page 28

background image

CONTROL PANEL OPERATING PROCEDURES

3-8

(a) Blower relay energizes and turns on

blower.

(b) Air/Fuel Valve rotates to the full-open

purge position and closes purge position

switch. The dial on the Air/Fuel Valve

(Figure 3-4) will read 100 to indicate that

the valve is full-open (100%).

(c) The

VALVE POSITION bargraph will

show 100%.

STEPPER

MOTOR

DETAIL "A"

DIAL

(DETAIL “A”)

100

BL

O

W

E

R

BU

R

N

ER

Figure 3-4.

Air/Fuel Valve In Purge Position

4. Next, the blower proof switch (Figure 3-5)

closes and the display will show Purging

and

indicate the elapsed time of the purge cycle

in seconds. The normal (default) time for the

purge cycle is 7 seconds.

154

155

AIR/FUEL VALVE

BLOWER PROOF

SWITCH

TO FRAME

HARNESS

Figure 3-5.

Blower Proof Switch

5. Upon completion of the purge cycle, the

Control Box initiates an ignition cycle and the

following events occur:
(a) The Air/Fuel Valve rotates to the low-fire

ignition position and closes the ignition

switch. The dial on the Air/Fuel Valve

(Figure 3-6) will read between 25 and 35

to indicate that the valve is in the low-

fire position.

(b) The igniter relay is activated and pro-

vides ignition spark.

(c) The gas Safety Shut Off Valve (SSOV)

is energized (opened) allowing gas to

flow into the Air/Fuel Valve.

6. Up to 7 seconds will be allowed for ignition to

be detected. The igniter relay will be turned

off one second after flame is detected.

7. After 2 seconds of continuous flame, Flame

Proven

will be displayed and the flame

strength will be indicated. After 5 seconds,

the current date and time will be displayed in

place of the flame strength.