MAINTENANCE

6-5

10. Carefully remove the lower tubing assembly taking care not to lose either the cold water or hot water

mixing orifice, (See Fig. 6.5).

11. Loosen the compression fitting holding the hydraulic zero and control orifice tube assembly to the

pump’s impeller housing, (See Fig. 6.6).

NOTE:

The cold water mixing orifice (P/N GP-122401) is slightly larger than the hot water mixing orifice (P/N GP-

122760). Each orifice must be correctly installed for proper temperature control.

HYDRAULIC ZERO &

CONTROL ORIFICE

TUBING ASSEMBLY

COLD WATER

MIXING ORIFICE

HOT WATER

MIXING ORIFICE

HYDRAULIC ZERO

NEEDLE VALVE

LOWER TUBING ASSEMBLY

Figure 6.5

BTU Transmitter Disassembly

COMPRESSION

FITTINGS

IMPELLER

HOUSING

PUMP OUTLET

TUBE

Figure 6.6

BTU Transmitter Pump Compression Fitting Locations