beautypg.com

11 fault relay, Figure 2.10 i/o box wiring, Installation – AERCO KC Series Equipped with C-More Controller for Massachusetts Only User Manual

Page 18

background image

INSTALLATION

2-8

INTL’K IN. Both interlocks, described below, are

factory wired in the closed position.

NOTE:

Both the Delayed Interlock and Remote

Interlock must be in the closed position to

allow the unit to fire.

2.6.10.1 REMOTE INTERLOCK IN

The remote interlock circuit (REMOTE INTL’K

IN) is provided to remotely start (enable) and

stop (disable) the unit if desired. The circuit is

24 VAC and comes factory pre-wired closed

(jumped).

2.6.10.2 DELAYED INTERLOCK

The delayed interlock circuit (DELAYED INTL’K

IN) is typically used in conjunction with the

auxiliary relay described in paragraph 2.6.11.

This interlock circuit is located in the purge

section of the start string. It can be connected to

the proving device (end switch, flow switch etc.)

of an auxiliary piece of equipment started by the

unit’s auxiliary relay. The delayed interlock must

be closed for the heater to fire. If the delayed

interlock is connected to a proving device that

requires time to close (make), a time delay (Aux

Start On Dly) that holds the start sequence of the

unit long enough for a proving switch to make

(close) can be programmed. Should the proving

switch not prove within the programmed time

frame, the unit will shut down. The Aux Start On

Dly can be programmed from 0 to 120 seconds.

This option is locate in the Configuration Menu

(Section 3).

2.6.11 FAULT RELAY

The fault relay is a single pole double throw

(SPDT) relay having a normally open and

normally closed set of relay contacts that are

rated for 5 amps at 120 VAC and 5 amps at 30

VDC. The relay energizes when any fault

condition occurs and remains energized until the

fault is cleared and the

CLEAR button is

depressed. The fault relay connections are

shown in Figure 2.10.

2.6.12 AUXILIARY RELAY CONTACTS

Each unit is equipped with a single pole double

throw (SPDT) relay that is energized when there

is a demand for heat and de-energized after the

demand for heat is satisfied. The relay is

provided for the control of auxiliary equipment,

such as pumps and louvers, or can be used as a

unit status indictor (firing or not firing). Its

contacts are rated for 120 VAC @ 5 amps.

Refer to Figure 2.10 to locate the AUX RELAY

terminals for wiring connections.

mA OUT

RS-485

COMM.

+

-

+

-

ANALOG IN

SENSOR COMMON

OUTDOOR SENSOR IN

REMOTE INTL'K IN

B.M.S. (PWM) IN

SHIELD

+

-

+

-

AUX SENSOR IN

NOT USED

EXHAUST SWITCH IN

DELAYED INTL'K IN

FAULT RELAY

120 VAC, 5A, RES

AUX RELAY

120 VAC, 5A, RES

G

RELAY CONTACTS:

120 VAC, 30 VDC

5 AMPS RESISTIVE

DANGER

120 VAC USED

IN THIS BOX

NOT USED

NOT USED

NC

COM

NO
NC

COM

NO

NOT USED

Figure 2.10 I/O Box Wiring