TROUBLESHOOTING

7-5

KC1000 WATER HEATER TROUBLESHOOTING TABLE – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

(continued)

3. Defective High Gas

Pressure Switch

3. Remove the leads from the high gas

pressure switch and measure continuity

across the common and normally closed

terminals with the unit not firing. Replace

the switch if it does not show continuity.

HIGH WATER TEMP

SWITCH OPEN

1. Scaled BTU

Transmitter.

2. Faulty Water

Temperature Switch.

3. Faulty Temperature

Sensor

4. Unit in MANUAL Mode

5. Unit setpoint is greater

than Over Temperature

Switch setpoint

1. Inspect and clean the BTU transmitter per

Maintenance Section.

2. Test the temperature switch to insure it

trips at its actual water temperature setting.

3. Using the resistance charts in Appendix C,

measure the resistance of Shell sensor and

BTU sensor at a known water temperature.

4. If unit is in Manual Mode, switch to Auto

Mode.

5. Check setpoint of unit and setpoint of

Temperature Switch. Ensure that the

temperature switch is set 20 degrees

higher than the unit’s setpoint.

HIGH WATER

TEMPERATURE

1. See HIGH WATER

TEMP SWITCH OPEN.

2. Temp HI Limit setting is

too low.

1. See HIGH WATER TEMP SWITCH OPEN


2. Check Temp HI Limit Setting.

IGN BOARD

COMM FAULT

1. Communication fault

has occurred between

the PMC board and

Ignition/Stepper (IGST)

board

1. Press CLEAR button and restart unit. If

fault persists, contact qualified Service

Personnel.