6 temperature control calibration, 1 setting the outlet water temperature setpoint, 2 minimum load adjustment – AERCO KC Series Equipped with C-More Controller for Massachusetts Only User Manual

Page 36: Initial start-up

background image

INITIAL START-UP

4-6

5. Reinstall the regulator cap and gasket on the

regulator. Tighten the cap using a

screwdriver or wrench.

6. Remove all of the manometers and barbed

fittings and reinstall the pipe plugs using a

suitable thread compound.

7. Remove the combustion analyzer probe

from the vent hole. Seal the probe hole and

replace the vent connection cover.

8. Replace the unit’s panels and hood.

4.6 TEMPERATURE CONTROL

CALIBRATION

Although the unit comes factory set and

calibrated for a 130°

F setpoint it is usually

necessary to recalibrate temperature control.

There are two primary adjustments for

performing temperature calibration. These are

Min Load Adj and Max Load Adj (minimum and

maximum load adjustment).

Adjustments to these settings are made at

minimum and maximum load conditions and

should be made in small increments from 1 to 3

degrees. After making an adjustment, outlet

water temperature must be allowed to settle for

several minutes prior to making further

adjustments.

When calibrating temperature control, observe

the following:

1. The unit must be in the Auto mode of

operation.

2. The Outlet Feedback option in the Tuning

Menu must be off while performing

calibration.

3. Monitor the

OUTLET TEMPERATURE

display and

VALVE POSITION bar-graph

display to set load conditions and see the

effect of adjustments.

4. Perform the calibration using the Tuning

Menu of the Control Box.

5. Make small adjustments and allow time

between adjustments for the outlet

temperature to stabilize.

6. Maintain water flow as constant as possible

during these adjustments.

7. Ensure that recirculation loops are

operational while the calibration is being

performed.

4.6.1 SETTING THE OUTLET WATER

TEMPERATURE SETPOINT

The setpoint temperature of the unit may be

changed by following the procedure below.

However, once a setpoint has been changed,

recalibration may be necessary.

The

temperature calibration procedures are provided

in paragraphs 4.6.2 and 4.6.3

To adjust the unit’s setpoint, proceed as follows:

1. Press the

MENU key until Configuration

Menu is displayed.

2. Press the ▲ or ▼ arrow key until Internal

Setpt is displayed along with the present

setpoint temperature.

3. To change the setpoint, press the

CHANGE

key. The display will begin to flash.

4. Press the ▲ or ▼ arrow key until the desired

setpoint is displayed.

5. Press the ENTER key to save the change.

4.6.2 MINIMUM LOAD ADJUSTMENT

With the unit in operation, check the temperature

control at minimum load as follows:

1. While monitoring the

VALVE POSITION

display, create a minimum load on the

system that will yield a steady valve position

between 25% and 35%.

NOTE:

It may be desirable to shut off the outlet valve and

use the hose bib to simulate a minimum flow load

condition.

2. Wait several minutes to allow the outlet

temperature to stabilize under load

conditions.

3. Once stabilized, the

OUTLET

TEMPERATURE display should read no

more than 2 to 3 degrees above the unit’s

setpoint.

4. If the outlet temperature is stabilized,

proceed to the Maximum Load Adjustment

procedure in paragraph 4.6.3. If the unit is

not stabilized, proceed to step 5.

5. Press the

MENU key and select the Tuning

Menu.

6. Press the ▲ or ▼ arrow key until Min Load

Adj is displayed.