Error Code
Message Information
LCD Message
PSU <
number
> is absent. Check PSU.
Details
The supply has been removed or has failed.
Action
1. Remove and reinstall the power supply.
2. Check cables and subsystem components in the system for
damage.
.
PSU0031
Message
Cannot communicate with power supply <
number
>.
LCD Message
Cannot communicate with PSU <
number
>. Re-seat PSU.
Details
The power supply may operate, however power supply monitoring
will be degraded. System performance may be degraded.
Action
Remove and reinstall the power supply. If the issue persists, see
PSU1201
Message
Power supply redundancy is lost.
Details
The power supply will try to operate in a degraded state. System
Performance and power redundancy may be degraded or lost.
Action
Check input power. Reinstall the power supply. If the issue persists,
see
.
PSU1202
Message
Power supply redundancy is degraded.
Details
The power supply will try to operate in a degraded state. System
Performance and power redundancy may be degraded or lost.
Action
Remove input power and reinstall supply at the next service window.
PSU1203
Message
The power supplies are not redundant.
LCD Message
Lost PSU redundancy. Check PSU cables.
Details
The current power operational mode is non-redundant because of a
power supply exception, a power supply inventory change, or a
system power inventory change.
Action
Check the event log for power supply failures. Review system
configuration and power consumption.
PSU1204
Message
The power supplies are not redundant. Insufficient resources to
maintain normal operations.
LCD Message
PSU redundancy degraded. Check PSU cables.