8 sp db: select “sp 1” and “sp 2” deadband, 10 out .cnf: control flashing of the display – Cooper Instruments & Systems DFI INFINITY Digital Force Indicator/Controller User Manual
Page 59

3.“ALF.3=0” makes “SP 4” INDEPENDENT, with a level equal to the value inserted for “SP 4”.
“ALF.3=1” assigns “SP 4” to “SP 2”, placing it ABOVE “SP 2” by the amount entered for “SP 4”.
“ALF.3=2” places “SP 4” BELOW “SP 2” by the amount entered for“SP 4”.
“ALF.3=3” places “SP 4” ON BOTH SIDES OF “SP 2” by the amount entered for “SP 4”.
4.“ALF.4=0” makes Alarm 2 (Setpoint 4) a NON-LATCHING Alarm.
“ALF.4=1” makes Alarm 2 (Setpoint 4) LATCHING. This means that once Alarm 2 (Setpoint 4) is triggered it will
remain active until it is reset by pressing the ‘RESET” button one time or by grounding P2-11 when configuration bit
“ALC.8=1” is set.
Reset can also be accomplished via the optional RS-232 or RS-485 serial communication board.
Press the ‘MENU’ button to store any changes and advance to “AL RDG” (Alarm Reading).
10.7 AL RDG: Alarm Readings-Select Delay In Alarm Action
This byte allows you to select the number of input readings required to trigger Alarm 1 (Setpoint 3) and Alarm 2
(Setpoint 4) action.
When “AL RDG” is displayed, press the ‘MIN’ button to see two 2-digit numbers, with the first one flashing,
indicating that you can reset the delay for SP3 by pressing the ‘MAX’ button.
After choosing “SP 3” delay, press the ‘MIN’ button and select the delay for “SP 4” by pressing the ‘MAX’ button.
Store your selections or changes by pressing the ‘MENU’ button and advance to “SP DB” (Setpoint Deadband).
10.8 SP DB: Select “SP 1” and “SP 2” Deadband (Hysteresis)
The deadband (hysteresis) for Setpoint 1 (“SP 1”) and Setpoint 2 (“SP 2”) is displayed with the same decimal point
location as chosen for run mode.
This selected hysteresis value is EVENLY SPLIT on both sides of the levels chosen for “SP 1” and “SP 2”.
View the value by pressing the ‘MIN’ button, reset by pressing the ‘MAX’ button, and store by pressing the ‘MENU’
button. Advance to “AL DB” (Alarm Deadband).
10.9 AL DB: Select Alarm 1 (SP 3) and Alarm 2 (SP 4) Deadband (Hysteresis)
This selected deadband (hysteresis) for Alarm 1 (“SP 3”) and Alarm 2 (“SP 4”) is placed on the INACTIVE side of
the selected levels. This results in immediate action (if zero (0) delay is selected in “AL RDG”) when an alarm limit
is exceeded, but defers recovery when the input returns to pre-alarm levels.
Press the ‘MIN’ button to view the values, change the values of each flashing digit by pressing the ‘MAX‘ button,
store any changes by pressing the ‘MENU’ button. Advance to “OUT.CNF” (Output Configuration).
10.10 OUT .CNF: Control Flashing Of The Display
You may wish to bring abnormal conditions to immediate attention by causing the display to flash.
Press the ‘MIN’ button to see “OUT.6”.
Press the ‘MAX‘ button to select “0”, “1”, “2”, “3”, “4”, or “5”.
“OUT.6=0” disables display flashing.
“OUT.6=1” flashes the display if SP1 is active.
“OUT.6=2” flashes the display if SP2 is active.
“OUT.6=3” flashes the display if SP3 is active.
“OUT.6=4” flashes the display if SP4 is active.
“OUT.6=5” flashes the display if any SP is active.
Save your choice or changes by pressing the ‘MENU’ button and the meter will momentarily display “STORED”,
then “RUN” and proceed with normal operation (go into run mode).
CF 67
54