L3d 3-wire and ecosystemr ulr listed driver, Wire controls, Ecosystem r controls – Diode LED Lutron Hi-Lume L3D User Manual
Page 2: Warranty, Compatible controls, L3d troubleshooting

3-Wire Controls
Product
Part Number
Drivers per Control
7
Measured
Light
Output Range
120 V~
277 V~
120 V~
277 V~
Nova T*
R
NTF-10-
NTF-10-277-
1 – 41
1 – 44
100% – 1%
NTF-103P-
NTF-103P-277-
1 – 20
1 – 33
100% – 1%
Nova
R
NF-10-
NF-10-277-
1 – 41
1 – 44
100% – 1%
NF-103P-
NF-103P-277-
1 – 20
1 – 33
100% – 1%
Skylark
R
SF-10P-
SF-12P-277-
1 – 20
1 – 33
100% – 1%
SF-103P-
SF-12P-277-3
1 – 20
1 – 33
100% – 1%
Diva
R
DVF-103P-
DVF-103P-277-
1 – 20
1 – 33
100% – 1%
DVSCF-103P-
DVSCF-103P-277- 1 – 20
1 – 33
100% – 1%
Ariadni
R
AYF-103P-
AYF-103P-277-
1 – 20
1 – 44
100% – 1%
Vierti
R
VTF-6A-
1 – 15
1 – 33
100% – 1%
Maestro
R
MAF-6AM-
MAF-6AM-277-
1 – 15
1 – 20
100% – 1%
MSCF-6AM-
MSCF-6AM-277-
1 – 15
1 – 20
100% – 1%
Maestro Wireless
R
MRF2-F6AN-DV-
1 – 15
1 – 33
100% – 1%
Lyneo
R
Lx
LXF-103PL-
LXF-103PL-277-
1 – 20
1 – 33
100% – 1%
RadioRA
R
2
RRD-F6AN-DV-
1 – 15
1 – 33
100% – 1%
HomeWorks
R
QS
HQRD-F6AN-DV
1 – 15
1 – 33
100% – 1%
Interfaces
8
PHPM-3F-120
1 – 41
–
100% – 1%
PHPM-3F-DV
1 – 41
1 – 88
100% – 1%
GP Dimming Panels
Various
1 – 41
1 – 88
100% – 1%
EcoSystemR Controls
Product
Part Number
Drivers per Control
Measured
Light
Output Range
120 V~
277 V~
120 V~
277 V~
PowPak
R
dimming Module
with EcoSystem
R
RMJ-ECO32-DV-B
32 per EcoSystem
R
link
100% – 1%
Energi Savr NodeT with
EcoSystem
R
QSN-1ECO-S, QSN-2ECO-S
64 per EcoSystem
R
link
100% – 1%
GRAFIK Eye
R
QS with
EcoSystem
R
QSGRJ-_E,
QSGR-_E
64 per EcoSystem
R
link
100% – 1%
Quantum
R
Various
64 per EcoSystem
R
link
100% – 1%
HomeWorks
R
QS with
EcoSystem
R
QSGRJ-_E, QSGR-_E, LQSE-2ECO-D
64 per EcoSystem
R
link
100% – 1%
7
No derating required in multigang applications provided that driver count does not exceed quantity listed.
8
For use with 3-wire controls in Commercial Systems, RadioRA
R
Systems, HomeWorks
R
or Home Systems applications.
Note: For information about Legacy product use in existing control application, contact [email protected]
Need Help? www.lutron.com/hilumeled or call the Lutron LED Center of Excellence at 1.877.346.5338
041436
Rev. A
01/2014
Warranty:
For warranty information, please visit:
www.lutron.com/BallastDriverWarranty
Lutron, , Hi-lume, Nova T*, Nova, Ariadni, Verti,
Lyneo, PowPak, EcoSystem, HomeWorks, GRAFIK
Eye, Skylark, Diva, Maestro, Maestro Wireless,
Quantum, and RadioRA, are registered trademarks
and RadioRA 2 and Energi Savr Node are trademarks
of Lutron Electronics Co. Inc.
©2013 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg PA, 18036-1299
Compatible Controls
• 3-Wire Controls
• EcoSystem
R
Controls
Please consult individual component installation for
more details.
Compatible Controls
For assistance selecting controls, contact our LED Center of Excellence at
1.877.346.5338 or
Driver Leads
Maximum driver-to-LED light engine wire length for
Constant Current Drivers:
Wire Gauge
Maximum Lead Length
200 mA to
700 mA
710 mA to
1.50 A
1.51 A to
2.10 A
18 AWG (0.75 mm
2
) 30 ft (9 m)
15 ft (4.5 m)
10 ft (3 m)
16 AWG (1.5 mm
2
)
35 ft (10.5 m)
25 ft (7.5 m)
15 ft (4.5 m)
14 AWG (2.5 mm
2
)
50 ft (15 m)
40 ft (12 m)
25 ft (7.5 m)
12 AWG (4.0 mm
2
)
100 ft (30 m)
60 ft (18 m)
40 ft (12 m)
Maximum driver-to-LED light engine wire length for
Constant Voltage Drivers:
Wire Gauge
Maximum Lead Length
10 V- to
20 V-
20.5 V- to
40 V-
40.5 V- to
60 V-
18 AWG (0.75 mm
2
) 10 ft (3 m)
15 ft (4.5 m)
30 ft (9 m)
16 AWG (1.5 mm
2
)
15 ft (4.5 m)
25 ft (7.5 m)
50 ft (15 m)
14 AWG (2.5 mm
2
)
25 ft (7.5 m)
40 ft (12 m)
75 ft (22.5 m)
12 AWG (4.0 mm
2
)
40 ft (12 m)
60 ft (18 m)
100 ft (30 m)
L3D Troubleshooting
LED does not
illuminate
• Verify that the system is wired correctly according to wiring
diagram.
• Verify that the LED load is wired correctly; red to positive,
black/white to negative.
• Verify that the LED load is compatible with the specified
voltage output of the driver.
• If using a constant voltage driver, verify that the LED load is for
“constant voltage” applications.
• If using a constant current driver, verify that the LED load is for
“constant current” applications.
• Lutron drivers are not for use with MR16 LED lamps.
LED does not dim
• Verify that Switched Hot and Dimmed Hot are connected to
the proper terminals.
LED exhibits a flash
or steppy dimming
on first use
• Drivers will “learn” the LED load on first startup. This is a
one-time event for a particular driver/LED combination.
Running the load at full output for 5 seconds should complete
“learning.”
LED is flashing,
flickering,
dropping out, or
has poor dimming
performance
• Verify that a compatible dimmer is being used to control the
driver.
• Verify that Switched Hot and Dimmed Hot are connected to
the proper terminals.
• If using a constant voltage driver, verify that the LED load is for
“constant voltage” applications.
• Verify that length of wires between driver and LED does not
exceed Lutron specification.
• Certain types of LED loads may be incompatible.
9
• Verify that the rated voltage is present at the driver.
• Lutron drivers are not for use with MR16 LED lamps.
LED is flashing slowly
(6 to 8 second
interval)
• If using a constant voltage driver, verify that your LED load
does not exceed the maximum specified power rating of the
driver (40 W).
• If using a constant voltage driver, verify that your LED load
matches the specified voltage output of the driver.
• If using a constant current driver, verify that your LED load falls
within the specified voltage rating of the driver.
• Verify that length of wire between driver and LED does not
exceed Lutron specification.
• Certain types of LED loads may be incompatible.
9
LED is dimming in
reverse
• Verify that Switched Hot and Dimmed Hot are connected to
the proper terminals.
LED output appears
dim at high-end
• Verify that the driver is operating in an environment within its
ambient temperature rating.
LED emits audible
noise at dimmed
levels
• Certain types of LED loads may be incompatible.
9
LED strip / array has
dark spots
• If using a constant current driver, check to see if dimming
parallel-wired LEDs with CCR driver; PWM is recommended
for these applications.
Not all LED strips /
fixtures illuminate
• Verify that multiple LEDs connected to a single driver are
properly wired.
9
Certain constant current loads may have additional circuitry and certain constant voltage loads may have
added capacitance. Contact the Lutron LED Center of Excellence at 1.877.346.5338 for more information
about these loads.
L3D 3-Wire and EcoSystemR
ULR Listed Driver
Compatible Controls