Rockwell Automation DeviceLogix System User Manual User Manual
Page 193

Publication RA-UM003B-EN-P - February 2010
193
RSNetWorx for DeviceNet Software and the DeviceLogix Editors Appendix B
Determine Network Status Override
The network status override parameter controls whether local logic
should control outputs when it detects a network error condition. You
determine if the network status override is enabled or disabled.
When the override is disabled (default), the device turns outputs off
under any of the events. If the override is enabled, the device ignores
any network fault. If DeviceLogix functionality is enabled, the control
of outputs is maintained even if there is a network fault.
The Network Status Override parameter is used to override normal
behavior during the following events.
Network Status Override Overview
Exemplary Network
Error Conditions for
DeviceNet
Behavior with Network Status
Override Parameter Disabled
Behavior with Network
Status Override Parameter
Enabled
Duplicate MAC ID
Failure
Module is put into an inoperable state
and all outputs remain off.
Local logic continues to update
output values.
Entering the bus off
state at power up
Module is put into an inoperable state
and all outputs remain off.
Local logic continues to update
output values.
Entering the bus off
state during run time
Module is put into an inoperable state
and all outputs assume a safe state.
Local logic continues to update
output values.