Troubleshooting

4-9

4.2.3 Fault Descriptions and Corrective Actions

Table 4.5 describes drive faults and corrective actions. It also indicates if the fault is
➀ Auto-resettable
➁ Non-resettable
➂ User-configurable

Table 4.5 – Fault Descriptions and Corrective Actions

Fault

No

.

Ty

p

e

Description

Action

Analog In
Loss

29

An analog input is configured
to fault on signal loss. A signal
loss has occurred.

Configure with Anlg In 1, 2
Loss (324, 327).

1.

Check parameters.

2.

Check for broken/loose
connections at inputs.

Anlg Cal
Chksum

108

The checksum read from the
analog calibration data does
not match the checksum
calculated.

Replace drive.

Auto Rstrt
Tries

33

Drive unsuccessfully
attempted to reset a fault and
resume running for the
programmed number of Auto
Rstrt Tries (174).

Enable/disable with Fault
Config 1 (238).

Correct the cause of the fault
and manually clear.

AutoTune
Aborted

80

The autotune procedure was
canceled by the user or a fault
occurred.

Restart procedure.

Auxiliary
Input

2

Input is open.

Check remote wiring.

Cntl Bd
Overtemp

55

The temperature sensor on
the Main Control Board
detected excessive heat.

1.

Check Main Control Board
fan.

2.

Check surrounding air
temperature.

3.

Verify proper
mounting/cooling.

DB
Resistance

69

Resistance of the internal DB
resistor is out of range.

Replace resistor.

Decel Inhibit

24

The drive is not following a
commanded deceleration
because it is attempting to limit
bus voltage.

1.

Verify input voltage is within
drive specified limits.

2.

Verify system ground
impedance follows proper
grounding techniques.

3.

Disable bus regulation
and/or add dynamic brake
resistor and/or extend
deceleration time.