Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 81
![background image](/manuals/580999/81/background.png)
Installing Power Wiring
6-11
Table 6.3 – Braking Resistor Capacity
Drive Rating
(Normal Duty
Motor
kW
Bus
Voltage
(VDC)
SP600
Absolute
Minimum
Resistance
(Zero
Tolerance)
Suggested
Resistance
with 10%
Tolerance
(SP600)
Peak
Power
(kW)
During
On Time
Resulting
Braking Torque
(expressed in% of
rated motor
torque)
240 V, 0.5 HP
0.37
395
30.38
131
1.08
293%
240 V, 1 HP
0.75
395
30.38
66
2.15
287%
240 V, 2 HP
1.5
395
30.38
61
2.33
155%
240 V, 3 HP
2.2
395
30.38
49
2.89
132%
240 V, 5 HP
4
395
27.43
33
4.30
107%
240 V, 7.5 HP
5.5
395
20.90
24
5.91
107%
240 V, 10 HP
7.5
395
20.90
24
5.91
79%
240 V, 15 HP
11
395
11.20
15
9.46
85%
240 V, 20 HP
15
395
9.00
14
10.13
68%
240 V, 25 HP
18.5
395
9.00
10
14.18
76%
400 & 480 V, 0.5 HP
0.37
790
61.72
502
1.13
305%
400 & 480 V, 1 HP
0.75
790
61.72
306
1.85
247%
400 & 480 V, 2 HP
1.5
790
61.72
163
3.48
232%
400 & 480 V, 3 HP
2.2
790
61.72
131
4.33
197%
400 & 480 V, 5 HP
4
790
61.72
97
5.85
146%
400 & 480 V, 7.5 HP
5.5
790
66.95
70
8.11
147%
400 & 480 V, 10 HP
7.5
790
66.95
73
7.77
104%
400 & 480 V, 15 HP
11
790
39.90
45
12.61
115%
400 & 480 V, 20 HP
15
790
27.82
45
12.61
84%
400 & 480 V, 25 HP
19
790
24.60
30
18.91
101%
400 & 480 V, 30 HP
22
790
29.10
30
18.91
84%
400 & 480 V, 40 HP
30
790
18.7
21
29.7
111%
400 & 480 V, 50 HP
37
790
18.7
21
29.7
89%
600 V, 0.5 HP
0.37
987.5
106.12
874
1.01
274%
600 V, 1 HP
0.75
987.5
106.12
471
1.88
251%
600 V, 2 HP
1.5
987.5
106.12
255
3.48
232%
600 V, 3 HP
2.2
987.5
106.12
209
4.24
193%
600 V, 5 HP
4
987.5
72.74
120
7.39
185%
600 V, 7.5 HP
5.5
987.5
72.74
82
10.81
197%
600 V, 10 HP
7.5
987.5
72.74
82
10.81
144%
600 V, 15 HP
11
987.5
43.62
48
18.47
168%
600 V, 20 HP
15
987.5
43.62
48
18.47
123%
600 V, 25 HP
18.5
987.5
Future
Future
Future
Future
600 V, 30HP
22
987.5
Future
Future
Future
Future
600 V, 40 HP
30
987.5
Future
Future
Future
Future
600 V, 50 HP
37
987.5
Future
Future
Future
Future