Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 216
12-86
SP600 AC Drive User Manual
Scales the analog output voltage at the source value maximum.
Scaling the Analog Output
You define the scaling for the analog output by entering analog
output voltages into Analog Out1 Lo and Analog Out1 Hi. These two
output voltages correspond to the bottom and top of the possible
range covered by the quantity being output. The output voltage will
vary linearly with the quantity being output. The analog output
voltage will not go outside the limits defined by Analog Out1 Lo and
Analog Out 1 Hi. See table 12.4.
Scales the analog output voltage at the source value minimum.
Refer to Analog Out1 Hi (343) for more information.
343
Analog Out1 Hi
Range:
0.00 to 10.00 Volts [0.01 Volt]
Default:
10.00 Volts
Access:
1
Path: Inputs & Outputs>Analog Outputs
See also:
342
Table 12.4 – Analog Output Scaling
Options:
Analog Out1 Lo (344) Value Corresponds to:
Analog Out1 Hi (343)
Value Corresponds to:
Analog Out Absolut (341)
= Disabled
Analog Out Absolut (341)
= Enabled
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Output Freq
Commanded Freq
Output Amps
Torque Amps
Flux Amps
Output Power
Output Volts
DC Bus Volts
PI Reference
PI Feedback
PI Error
PI Output
%Motor OL
%Drive OL
–[Maximum Freq]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
0 Hz
0 Hz
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
+[Maximum Freq]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated
200% Rated
100%
100%
100%
100%
100%
100%
344
Analog Out1 Lo
Range:
0.00 to 10.00 Volts [0.01 Volts]
Default:
0.00 Volts
Access:
1
Path: Inputs & Outputs>Analog Outputs
See also:
342, 343