Parameter Descriptions

12-79

Parameter number whose value will be written to a communications
device data table. See figure 12.48.

Selects the type of input signal being used for analog input 1 and 2.
These inputs can be configured as 10 VDC or 4-20 mA inputs. See
scaling parameters 322, 323 (Analog In1) and 325, 326 (Analog
In2).

316
317

Data Out D1 - Link D Word 1
Data Out D2 - Link D Word 2

Range:

0 to 387 [1]

Default:

0 (Disabled)

Access:

2

Path: Communication>Datalinks

See also:

320

Anlg In Config

Range:

See figure 12.49

Default:

See figure 12.49

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

322, 323, 325, 326

Figure 12.49 – Anlg In Config (320)

0

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Current
0 =Voltage
x =Reserved

Bit #

Factory Default Bit Values

Analog In 1

Analog In 2

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Analog In1

Bit

Term

0 to 10 VDC

Bit 0 = 0

14, 15

4 to 20 mA

Bit 0 = 1

16, 17

Analog In2

Bit

Term

-10 to +10 VDC

Bit 1 = 0

18, 19

4 to 20 mA

Bit 1 = 1

20, 21