Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 218
![background image](/manuals/580999/218/background.png)
12-88
SP600 AC Drive User Manual
Assigns an input function to the drive’s digital inputs. Note that
digital inputs Run, Jog, Stop, Clear-Faults, and Direction control
functions are operational only when the terminal block is selected
as the control source (Logic Source Sel = Terminal Blk).
The input functions are:
1 = Enable: If the input is closed, the drive can run (start
permissive). If the input is open, the drive will not start.
If the drive is already running when this input is opened, the drive
will coast and indicate “not enabled” on the OIM (if present). This is
not considered a fault condition, and no fault will be generated.
If multiple enable inputs are configured, the drive will not run if any
of them are open.
1
When Digital In”x” Sel is set to option 2 (Clear Faults), the Stop key cannot
be used to clear a fault condition.
2
Typical 3-wire inputs. These require that only 3-wire functions are chosen.
Including 2-wire selections will cause a type 2 alarm.
3
Typical 2-wire inputs. These require that only 2-wire functions are chosen.
Including 3-wire selections will cause a type 2 alarm.
4
To access Preset Speed 1, set Speed Ref A Sel to Preset Speed 1. See
table 12.5.
Table 12.5 – Speed Select Inputs
Speed Select
Inputs
3
2
1
Reference Source
0
0
0
Speed Ref A Sel (90)
0
0
1
Preset Speed 1 (101)
0
1
0
Preset Speed 2 (102)
0
1
1
Preset Speed 3 (103)
1
0
0
Preset Speed 4 (104)
1
0
1
Preset Speed 5 (105)
1
1
0
Preset Speed 6 (106)
1
1
1
Preset Speed 7 (107)
Table 12.6 – Default Values for Parameters 361-366
Parameter No.
Default Value
361
4 = Stop - CF
362
5 = Start
363
3 = Function Loss
364
10 = Jog
365
18 = Auto/Manual
366
15 = Speed Sel 1