Rockwell Automation SP600 AC Drive User Manual Version 1.0 User Manual
Page 140

12-10
SP600 AC Drive User Manual
Set to the motor nameplate rated frequency. The motor nameplate
base frequency defines the output frequency when operating at
rated voltage, rated current, rated speed, and rated temperature.
Set to the motor nameplate rated RPM. The motor nameplate RPM
defines the rated speed when operating at motor nameplate base
frequency, rated current, base voltage, and rated temperature. This
is used to calculate slip.
Set to the motor nameplate rated power. The motor nameplate
power is used with the other nameplate values to calculate default
values for motor parameters to assist the commissioning process.
This may be entered in horsepower or in kilowatts as selected in
parameter 46.
Set to the power units shown on the motor nameplate. This
parameter determines the units for parameter 45.
43
Motor NP Hertz
Range:
5.0 to 400.0 Hz [0.1 Hz]
Default:
Based on Drive Type
Access:
1
Path: Motor Control>Motor Data
See also:
44
Motor NP RPM
Range:
60 to 24000 RPM [1 RPM]
Default:
1750 RPM
Access:
1
Path: Motor Control>Motor Data
See also:
45
Motor NP Power
Range:
0.00 to 100.00 [0.01]
Default:
Based on Drive Type
Access:
1
Path: Motor Control>Motor Data
See also:
46
32
46
Mtr NP Pwr Units
Range:
0 = Horsepower
1 = kiloWatts
Default:
Based on Drive Type
Access:
2
Path: Motor Control>Motor Data
See also: