Parameter Descriptions

12-101

Sets the off delay time for the digital outputs. This is the time
between the disappearance of a condition and de-activation of the
relay.

387

Dig Out2 OffTime

Range:

0.00 to 600.00 Sec [0.01 Sec]

Default:

0.00 Sec

Access:

2

Path: Inputs & Output>Digital Outputs

See also:

384

Figure 12.54 – Dig Out2 OffTime (387)

Comparator

Delay
Timer

Output

Frequency

(384)

Dig Out2

Level (385)

Dig Out2

OnTime

(386)

Relay Out2

(Term 24, 25, 26)

Dig Out2

OffTime

(387)