Parameter Descriptions

12-53

Selects the method for control of drive direction.

0 = Unipolar: The drive receives an unsigned reference signal and
a separate direction command from a logic source such as a digital
input or DPI port device.

Example: Analog speed reference = 0 to 100%

Direction control:

• OIM Forward/Reverse key

• Terminal block

1 = Bipolar: The drive receives a signed reference (-100% to
+100%). In this case, the Forward/Reverse key has no effect.

2 = Reverse Dis: The drive receives a signed reference (-100% to
+100%); however, regardless of the reference, the drive is not
permitted to reverse.

Note: Internal reference scaling provides 100% = 32767 internal
units.

190

Direction Mode

Range:

0 = Unipolar
1 = Bipolar
2 = Reverse Dis

Default:

0 = Unipolar

Access:

0

Path: Utility>Direction Config

See also:

91, 92, 320 - 327, 361 - 366

!

ATTENTION: Setting parameter 190 to 0 or 1 may
cause unwanted motor direction. Verify driven
machinery cannot be damaged by reverse rotation
before changing the setting of this parameter to 0 or
1. Failure to observe this precaution could result in
damage to, or destruction of, equipment.

Parameter 190

Selection

Analog Reference

Direction Control

0 = Unipolar

0 to 100%

Logic

1 = Bipolar

-100% to +100%

Reference polarity

2 = Reverse Disable

-100% to +100%

Reverse disabled