Wiring Requirements for the Drive
4-11
Table 4.6 – SP600 400/480 VAC Input Recommended Protection Devices
Model
Number
kW
Dual Element
Time Delay
Fuse
Non-time
Delay Fuse
Circuit
Breaker
1
ND
HD
Min
2
Max
3
Min
2
Max
3
Max
4
400 VAC Input
6SP401-1P1
0.37
0.25
3
3
3
5
15
6SP401-2P1
0.75
0.55
4
6
4
8
15
6SP401-3P4
1.5
1.1
6
6
6
12
15
6SP401-005
2.2
1.5
10
10
10
20
20
6SP401-008
4
3
15
17.5
15
30
30
6SP401-011
5.5
4
15
25
15
45
40
6SP401-014
7.5
5.5
20
30
20
60
60
6SP401-022
11
7.5
30
45
20
80
80
6SP401-027
15
11
40
60
40
120
120
6SP401-034
18.5
15
45
80
45
125
125
6SP401-040
22
18.5
60
90
60
150
150
6SP401-052
30
22
80
125
80
225
240
6SP401-065
37
30
90
150
90
250
280
Model
Number
HP
Dual Element
Time Delay
Fuse
Non-time
Delay Fuse
Circuit
Breaker
1
ND
HD
Min
2
Max
3
Min
2
Max
3
Max
4
480 VAC Input
6SP401-1P1
0.5
0.33
3
3
3
4
15
6SP401-2P1
1
0.75
6
6
3
8
15
6SP401-3P4
2
1.5
6
6
6
12
15
6SP401-005
3
2
10
10
10
20
20
6SP401-008
5
3
15
15
15
30
30
6SP401-011
7.5
5
15
20
15
40
40
6SP401-014
10
7.5
20
30
20
50
50
6SP401-022
15
10
25
45
25
80
80
6SP401-027
20
15
35
60
35
100
100
6SP401-034
25
20
40
70
40
125
125
6SP401-040
30
25
50
90
50
150
150
6SP401-052
40
30
60
110
60
200
200
6SP401-065
50
40
80
125
80
250
250
1
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA.
Ratings shown are maximum
2
Minimum protection device size is the lowest rated device that supplies maximum
protection without nuisance tripping.
3
Maximum protection device size is the highest rated device that supplies drive protection.
For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
4
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.