Mounting the Drive
3-5
3.1.2 Making Sure Environmental Conditions are Met
Before deciding on an installation site, consider the following
guidelines:
•
Verify that NEMA 1 drives can be kept clean, cool, and dry.
•
The area chosen should allow the space required for proper air
flow as defined in section 3.1.3.
•
Be sure that NEMA 1 drives are away from oil, coolants, or other
airborne contaminants.
•
Do not install the drive more than 3300 feet above sea level
without derating output power. For every 300 feet above 3300
feet, derate the output current 1%.
•
Verify that the drive location will meet the environmental
conditions in Appendix A.
Figure 3.2 – Selecting Input Phase and Fan Voltage (60HP and Larger)
480 Volt Tap
600 Volt Tap
690 Volt Tap
400 Volt Tap
WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75
° C CU WIRE ONLY
POWER TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)