11-34

SP600 AC Drive User Manual

Sets the lower limit of the PI output. This value must be less than
the value set in PI Upper Limit (132).

Sets the upper limit of the PI output. This value must be greater than
the value set in PI Lower Limit (131).

Sets the value used to load into the PI Integrator while the PI
regulator is disabled. This allows better dynamic performance when
the regulator is enabled.

131

PI Lower Limit

Range:

-/+Maximum Freq [0.1 Hz]

Default:

-Maximum Freq

Access:

2

Path: Speed Command>Process PI

See also:

80, 124-138

132

PI Upper Limit

Range:

-/+Maximum Freq [0.1 Hz]

Default:

+Maximum Freq

Access:

2

Path: Speed Command>Process PI

See also:

80, 124-138

133

PI Preload

Range:

-/+Maximum Freq [0.1 Hz]

Default:

0.0 Hz

Access:

2

Path: Speed Command>Process PI

See also:

80, 124-138

Figure 11.12 – PI Preload Value

Preload Value

Spd Cmd

PI_Config

PreLoadCmd

PI_Status
Enabled

PI Integrator

(124)

(134)

(133)