Parameter Descriptions

11-73

Parameter number whose value will be written from a network
communications device data table.

Parameters that can only be changed while the drive is stopped
cannot be used as Datalink inputs. Entering a parameter of this type
will disable the link.

Refer to the appropriate communications option board manual for
Datalink information.

Parameter number whose value will be written from a
communications device data table.

Parameters that can only be changed while the drive is stopped
cannot be used as Datalink inputs. Entering a parameter of this type
will disable the link.

Refer to the appropriate communications option board manual for
Datalink information.

300
301

Data In A1 - Link A Word 1
Data In A2 - Link A Word 2

Range:

0 to 387 [1]

Default:

0 (Disabled)

Access:

2

Path: Communication>Datalinks

See also:

Network

Network
Card

Data

P#

SP600

Data In

(parameter #)

Data Received by Drive from Network

302
303

Data In B1 - Link B Word 1
Data In B2 - Link B Word 2

Range:

0 to 387 [1]

Default:

0 (Disabled)

Access:

2

Path: Communication>Datalinks

See also: