Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 123
Parameter Descriptions
11-21
Sets the center of a frequency band at which the drive will not
operate continuously (also called an avoidance frequency).
Requires that both a Skip Frequency and Skip Frequency Band (87)
be set to a value other than 0.
Determines the bandwidth around a skip frequency (half the band
above and half the band below the skip frequency).
Important: The drive is shipped with a default configuration of
control from the Local OIM (keypad). For drive control
from the terminal block inputs, Logic Source Sel (89),
must be set to 0.
• Terminal Blk = Hardwired I/O
• Local OIM = Drive-mounted OIM
• DPI Port 2 = DIN connector DPI port
• DPI Port 3 = DIN port 2 split with option cable
• Network = Communication interface
• All Ports = All control sources active
84
85
86
Skip Frequency 1
Skip Frequency 2
Skip Frequency 3
Range:
-/+400.0 [0.1 Hz]
Default:
0.0 Hz
Access:
84=2
85=2
86=2
Path: Speed Command>Spd Mode & Limits
See also:
87
87
Skip Freq Band
Range:
0.0 to 30.0 Hz [0.1 Hz]
Default:
0.0 Hz
Access:
2
Path: Speed Command>Spd Mode & Limits
See also:
84, 85, 86
89
Logic Source Sel
Range:
0 = Terminal Blk
1 = Local OIM
2 = DPI Port 2
3 = DPI Port 3
4 = Reserved
5 = Network
6 = Reserved
7 = All Ports
Default:
1 = Local OIM
Access:
0
Path: Speed Command>Control Src Select
See also:
90