82 Configure the Adapter for Master/Slave Communication
• an error bit in the poll response data is set
• a diagnostic bit in the Ext_Diag_Data field returned in the Read DP-Slave
Diagnostic Information message response is set
All eight slots must be configured with the module key parameter. The size for
this format depends on the module types which are configured (1 word ID for
standar modules, 2 word ID for EDT modules). The range can vary from
20 bytes (including the flags byte) to 36 bytes.
The condensed format structure must be repeated for each of the eight slots.
The following table shows the identification numbers for commonly used FLEX
I/O modules.
Data Format for Condensed Format
Name
Size
Description
Module Key
WORD
Module ID # that must be installed
(1)
(1)
Only bits 0…12 are used. Bits 13…15 must be zero except when keying an empty slot where 0FFFFh is used.
FLEX I/O Module Catalog Number
Module Identification Number
(module key)
Four-word Modules
1794-IB8
0180h
1794-OB8
0190h
1794-IB16
0281h
1794-OB16
0191h
1794-IV16
0204h
1794-OV16
010Ch
1794-IA8
0285h
1794-OA8
0195h
1794-OA8I
019Ch
1794-OW8
0199h
Sixteen-word Modules
1794-IE8/A
1920h
1794-OE4/A
1121h
1794-IE4XOE2/A
1522h
1794-IE8/B
1924h
1794-OE4/B
1125h
1794-IE4XOE2/B
1526h
1794-IT8
1B00h
1794-IR8
1B01h
1794-IRT8
1B03h
1794-ID2/B
1B03h