Publication 1794-UM064B-EN-P - May 2014
Device Data Base (GSD) File 109
For example, an I/O module has the following RTD (Real Time data)
I/O Profile:
In the Teaching entry in the GSD file, all the input, output and configuration
data are RTD (Real Time Data) / Cyclic Data, not the EDT I/O and
configuration data.
9
Length of status information in bits
10
Start address of digital output in bits
11
Length of digital output in bits
12
Start address of analog outputs in bits
13
Length of analog outputs in bits
14
Start address of configuration in bits
15
Length of configuration in bits.
16
17
Special module settings
(1)
See
Ext_User_Prm_Data_Const(0) Byte Description and Examples for Non-EDT Modules on page 109
for
more details about each byte.
Example RTD I/O Profile for Sample Non-EDT Module
RTD Index
Assembly Index
Assembly
RTD 0
MSW
Module Status Word
RTD 1...8
I:0...I:7
RTD Status Data
RTD 9...10
S0:...S1
RTD Status Data
RTD 11
O:0
RTD Output Word
RTD 12...13
C0:...C1
RTD Configuration Word
Ext_User_Prm_Data_Const(0) Parameter Byte Information
(1)
for Non-EDT Modules
Byte
Definition
Ext_User_Prm_Data_Const(0) Byte Description and Examples for Non-EDT Modules
Byte
Description
Example
Byte 1
Bits 0...12 of first two bytes are used for module ID and bits
13...15 must be set to "010" (0x40) to put the adapter into
the Teaching mode.
For example, if the module ID is 0x15, 0x03, then first byte
of Module ID is 0x55 (0x15 + 0x40).
Ext_User_Prm_Data_Const(0) =
0x55, 0x03, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX0, 0xXX0, 0xXX
Byte 2
Second byte of Module ID.
Ext_User_Prm_Data_Const(0) =
0x55, 0x03, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX0, 0xXX0, 0xXX
Byte 3
This byte should always be 0x00 in a teaching entry.
Ext_User_Prm_Data_Const(0) =
0x55, 0x03, 0x00, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX0, 0xXX0, 0xXX