Communicate With Your Module 33
1794-IT8 Word/Bit Descriptions
Word
Decimal Bit
Definition
Read Word 0
00…15 (00…17)
Reserved
Read Word 1
00…15 (00…17)
Channel 0 Input data
Read Word 2
00…15 (00…17)
Channel 1 Input data
Read Word 3
00…15 (00…17)
Channel 2 Input data
Read Word 4
00…15 (00…17)
Channel 3 Input data
Read Word 5
00…15 (00…17)
Channel 4 Input data
Read Word 6
00…15 (00…17)
Channel 5 Input data
Read Word 7
00…15 (00…17)
Channel 6 Input data
Read Word 8
00…15 (00…17)
Channel 7 Input data
Read Word 9
00…07 (00…07)
Underrange bits – These bits are set if the input signal is
below the input channel’s minimum range.
08…15 (10…17)
Overrrange bits – These bits are set if 1), the input signal
is above the input channel’s maximum range, or 2), an open
detector is detected.
Read Word 10
00
Not used – set to 0.
01
Cold Junction sensor underrange bit – This bit is set if
the cold junction temperature is below 0 °C.
02
Cold Junction sensor overrange bit – This bit is set if
the cold junction temperature is above 70 °C.
03
Power Up bit – This bit is set (1) until configuration data is
received by the module.
04…06
Critical Fault bits – If these bits are anything other than
zero, return the module to the factory for repair.
07
Unused – Set to 0.
08 (10)
Calibration Out of Range bit – Set to 1 if a reference
signal is out of range during calibration.
09 (11)
Calibration Done bit – Set to 1 after an initiated
calibration cycle is complete.
10 (12)
Calibration Bad bit – Set to 1 if the channel has not had a
valid calibration.
11…15 (13…17)
Unused – Set to 0.