Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 125
Publication 1794-UM064B-EN-P - May 2014
Device Data Base (GSD) File 113
6
Configuration Data Sizes Reserved in Teaching Mode (0).
7
Start address of digital input in bits.
8
Length of digital input in bits.
9
Start address of analog input in bits.
10
Length of analog input in bits.
11
Start address of status information in bits.
12
Length of status information in bits.
13
Start address of digital output in bits.
14
Length of digital output in bits.
15
Start address of analog output in bits.
16
Length of analog output in bits.
17
Start address of configuration in bits.
18
Length of configuration in bits.
19
20
Special module settings.
(1)
See
Ext_User_Prm_Data_Const(0) Byte Description and Examples for Non-EDT Modules on page
109
for more details about each byte.
Ext_User_Prm_Data_Const(0) Parameter Byte Information
(1)
for EDT Modules
Byte
Definition
Ext_User_Prm_Data_Const(0) Byte Description and Examples for EDT Modules
Byte
Description
Example
Byte 1...2
Bits 0...12 of the first two bytes are used for Module
ID and bits 13...15 must be set to "010" to put the
adapter into the teaching mode.
If Module ID of the module is 0x15, 0x01, then first byte
is 0x55.
Ext_User_Prm_Data_Const(0) =
0x55, 0x01, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX0, 0xXX0, 0xXX
Byte 3...4
Third and fourth bytes of the user module ID that
uniquely identifies EDT module and the catalog
identity.
If user module ID is 0xA0, 0x00, then third and fourth bytes
is as follows:
Ext_User_Prm_Data_Const(0) =
0x55, 0x01, 0xA0, 0x00, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX0, 0xXX0, 0xXX
Byte 5...6
Always 0x00 in teaching entry.
Ext_User_Prm_Data_Const(0) =
0x55, 0x01, 0xA0, 0x00, 0x00, 0x00,\
0xXX, 0xXX, 0xXX, 0xXX, 0xXX, 0xXX,\
0xXX, 0xXX, 0xXX0, 0xXX0, 0xXX
Byte 7
The start address of digital input in bits.
For digital input modules, the start address (in bits) of input (RTD2),
based on
Example RTD I/O Profile for Sample EDT Module on page
112
, is 16(RTD0) + 16 (RTD1) = 32 bits, that is 0x20.
For analog input modules and non-input modules, this byte is 0x00.