Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 141
Publication 1794-UM064B-EN-P - May 2014
128 Additional HART Protocol Information
Common Practice Commands
Command
Data in Command
Data in Reply
#
Function
Byte
Data
Type
(5)
Byte
Data
Type
33
Read transmitter
variables
—
None
(2)
—
0
Transmitter variable code
for slot 0
—
1
Units code for slot 0
2…5
Variable for slot 0
(F)
6
Transmitter variable code
for slot 1
—
7
Units code for slot 1
8…11
Variable for slot 1
(F)
12
Transmitter variable code
for slot 2
(6)
—
13
Units code for slot 2
14…17
Variable for slot 2
(F)
18
Transmitter variable code
for slot 3
—
19
Units code for slot 3
20…23
Variable for slot 3
(F)
34
Write damping value
0…3
Damping value (seconds)
(F)
—
As in command
(F)
35
Write range values
0
Range units code
—
—
As in command
(F)
1…4
Upper range value
(F)
—
5…8
Lower range value
(F)
36
Set upper range value
(push SPAN button)
—
None
—
—
None
—
37
Set lower range value
(push ZERO button)
—
None
—
—
None
—
38
Reset configuration
changed flag
—
None
—
—
None
—
39
EEPROM control
0
(1)
EEPROM control code
—
—
As in command
—
40
Enter/edit fixed current
mode
0…3
Current (mA)
(3)
(F)
—
As in command
—
41
Perform device
self-test
—
None
—
—
None
—
42
Perform master reset
—
None
—
—
None
—
43
Set (trim) PV zero
—
None
—
—
None
—
44
Write PV units
0
PV units code
—
—
As in command
—
45
Trim DAC zero
0…3
Measured current (mA)
—
—
As in command
—
46
Trim DAC gain
0…3
Measured current (mA)
(F)
—
As in command
—
47
Write transfer function
0
Transfer function code
—
—
As in command
—