Rockwell Automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual User Manual
Page 66
Publication 1794-UM064B-EN-P - May 2014
54 Communicate With Your Module
Write Word 6
IC
1
TR
IT
Q1
Q0
0
0
RV
QK
CK
GO
Channel Number
Write Word 7
Not used
Where:
PU = Power up unconfigured state
FP = Field power off
CF = Configuration mode
BD = Calibration bad
DN = Calibration accepted
P0 and P1 = Output holding in response to Q0...Q1
W0 and W3 =Wire off current loop status for channels 0 and 1 respectively. (Not used on voltage outputs).
U0 and U1 = Underrange for input channels 0 and 1 respectively
V0 and V1 = Overrange for input channels 0 and 1 respectively
EN = Enable outputs; 0 = output follows S1/S0, 1 = output enabled
IC = Initiate configuration bit
TR = Transparent bit
IT = Interrupt toggle bit
Q0 and Q1 = Hold
RV = Revert to defaults bit
QK = Quick calibration
CK = Calibration clock
GO = Gain offset select
Configure Your Input Channels
Input Channel Configuration
0
3
0
2
0
1
0
0
Set these bits for Channel 0
0
7
0
6
0
5
0
4
Set these bits for Channel 1
Bit Settings
Input
Values
Data Format
% Underrange/
% Overrange
Input Range
(2)
Hexadec. Dec.
Module Update Rate
(RTSI = 0) (RTSI = 0), IT = 1
0
0
0
0
Channel not configured
0
0
0
1
4...20 mA
signed 2’s complement
4% Under; 4% Over
<0000...7878>
<0000...30840>
7.5 ms
5.0 ms
0
0
1
0
± 10V
signed 2’s complement
2% Under; 2% Over
<831F...7CE1>
<-31969...31969>
2.5 ms
2.5 ms
0
0
1
1
± 5V
signed 2’s complement
4% Under; 4% Over
<8618...79E8>
<-31208...31208>
2.5 ms
2.5 ms
0
1
0
0
0...20 mA
signed 2’s complement %
0% Under; 4% Over
<0...2710>
<0...10000>
7.5 ms
5.0 ms
0
1
0
1
4...20 mA
signed 2’s complement %
4% Under, 4% Over
<0...2710>
<0...10000>
7.5 ms
5.0 ms
0
1
1
0
0...10V
signed 2’s complement %
0% Under; 2% Over
<0...2710>
<0...10000>
5.0 ms
5.0 ms
0
1
1
1
± 10V
singed 2’s complement %
2% Under; 2% Over
<-D8F0...2710>
<-10000...10000>
5.0 ms
5.0 ms
1
0
0
0
0...20 mA
binary
0% Under; 4% Over
<0000...F3CF>
<0000...62415>
2.5 ms
2.5 ms
1
0
0
1
4...20 mA
(1)
binary
4% Under; 4% Over
<0000...F0F1>
<0000...61681>
7.5 ms
5.0 ms
1
0
1
0
0...10V
binary
0% Under; 2% Over
<0000...F9C2>
<0000...63938>
2.5 ms
2.5 ms
1
0
1
1
0...5V
binary
0% Under; 4% Over
<0000...F3CF>
<0000...62415>
2.5 ms
2.5 ms
1
1
0
0
± 20 mA
offset binary, 8000H = 0 mA 4% Under; 4% Over
<0618...F9E8>
<1560...63976>
2.5 ms
2.5 ms
1
1
0
1
4...20 mA
offset binary, 8000H = 4 mA 4% Under; 4% Over
<8000...F878>
<32768...63608>
7.5 ms
5.0 ms
1
1
1
0
± 10V
offset binary, 8000H = 0V
2% Under, 2% Over
<031F...FCE1>
<799...64737>
2.5 ms
2.5 ms
± 5V
offset binary, 8000H = 0V
4% Under, 4% Over
<0618...F9E8>
<1560...63976>
2.5 ms
2.5 ms
(1)
Underrange for 4...20 mA occurs in the blind area below 0 (3.2 mA).
1794-IF2XOF2I – Isolated Analog Combo Module Read Words
Word/Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word/Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00