Specifications
E-3
7000 “A” Frame
7000A-RM001A-EN-P – January 2011
Description
Specifications
Control Power
220/240 V or 110/120 V, 1 phase – 50/60 Hz (20 Amp)
External I/O
16 Digital Inputs, 16 Digital Outputs
External Input Ratings
50/60 Hz AC or DC
120-240 V – 1 mA
External Output Ratings
50-60 Hz AC or DC
30-260 V – 1 amp
Analog Inputs
(3) Isolated, 4-20mA or 0-10 V
Analog Resolution
• Analog input 12 Bit (4-20 mA)
• Analog input 13 Bit (0-10V)
Analog Outputs
• (1) Isolated, 4-20 mA
• (8) Non-isolated, 0-10 V
Communication Interface
DPI
Scan Time
Internal DPI – 2 ms min., 4 ms max.
Communications Protocols
(Optional)
R
I/O
Lon
Works
DeviceNet
CAN
open
Ethernet
RS485
HVAC
Profibus
RS485
DF1
Modbus
RS232
DF1
Interbus
USB
ControlNet
Enclosure
NEMA 1, IP21
Lifting Device
Standard / Removable
Mounting Arrangement
Mounting Sill Channels
Structure Finish
Epoxy Powder – Paint
Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)
Internal – Control Sub Plates – High Gloss White (RAL 9003)
Interlocking
Key provision for customer input Disconnecting Device
Corrosion Protection
Unpainted Parts (Zinc Plates / Bronze Chromate)
Fiber Optic Interface
Rectifier – Inverter – Cabinet (Warning/Trip)
Door Filter
Painted Diffuser with Matted Filter Media
Door Filter Blockage
Air Flow Restriction Trip/Warning
Ambient Temperature
0° to 40°C (32°F to 104°F)
0° to 50°C (32°F to 122°F) Optional
Storage and Transportation
Temperature Range
-40°C to 70°C (-40°F to 185°F)
Relative Humidity
95% Non-Condensing
Altitude (Standard)
0 to 3300 ft. (0 to 1000 m)
Altitude (Optional)
0 to 16400 ft. (1001 to 5000 m)
Seismic (UBC Rating)
1, 2, 3, 4
Standards
NEMA, IEC, CSA, UL, ANSI, IEEE