7000 “A” Frame
Table 5.E – Test Points on Analog Control Board (cont.)
Test points
Name
Description
ACB-TP51
CP1
Control Power monitoring for channel 1
ACB-TP52
CP2
Control Power monitoring for channel 2
ACB-TP53
CP3
Control Power monitoring for channel 3
ACB-TP54
CP4
Control Power monitoring for channel 4
ACB-TP55
Vltrp
AC Over Voltage Detection set point for 2UVW&3UVW
ACB-TP56 AGND
Analog
ground
ACB-TP57 AGND
Analog
ground
ACB-TP58 AGND
Analog
ground
ACB-TP59 AGND
Analog
ground
ACB-TP60
+5V
+5V DC power supply
ACB-TP61
+15V
+15V DC power supply
ACB-TP62
-15V
-15V DC power supply
ACB-TP63
+24V
+24V DC power supply
ACB-TP64
-24V
-24V DC power supply
ACB-TP65
24VCOM
+/- 24V common
ACB-TP66 DGND
Digital
ground
ACB-TP67 AGND
Analog
ground
ACB-TP68
AP1
Analog Control Inputs, Air pressure input, AP1
ACB-TP69
AP0
Analog Control Inputs, Air pressure input, AP0
ACB-TP70
AIN1
Analog Control Input ,AIN1
ACB-TP71
AIN2
Analog Control Input ,AIN2
ACB-TP72
AIN0
Analog Control Input ,AIN0
ACB-TP73
AIN3
Analog Control Input ,AIN3
ACB-TP74
IPIS
Input Isolating Switch
ACB-TP75
IPCS
Input Contactor Status
ACB-TP76
IP
Input Contactor Command
ACB-TP77
OPIS
Output Isolating Switch
ACB-TP78 OPCS
Output
Contactor
Status
ACB-TP79 OP
Output
Contactor
Command
ACB-TP80
BPIS
Bypass Isolating Switch
ACB-TP81 BPCS
Bypass
Contactor
Status
ACB-TP82 BP
Bypass
Contactor
Command
ACB-TP83
DGND
Digital Ground Return
ACB Analog Control