beautypg.com

Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual

Page 396

background image

D-6

Preventative Maintenance Schedule

7000A-RM001A-EN-P – January 2011

7000 “A” Frame


Time Estimations

Operational Maintenance

0.5 hours per filter

Annual Maintenance

Initial Information Gathering

0.5 hours

Physical Checks

Torque Checks

2.0 hours

Inspection 2.0

hours

Cleaning **

2.5 hours **

Meggering 1.5

hours

Control Power Checks

Contactor Adjustments **

2.0 hours **

Voltage Level Checks

1.0 hours

Firing Check

0.5 hours

System Test **

2.0 hours **

Medium Voltage Checks

Final Inspection

0.5 hours

Phasing Check **

1.5 hours **

Autotuning**

2.0 hours **

Operation to Maximum Load

Site Dependent

Additional Tasks

Investigation **

Depends on Nature of the Problem **

Informal Training/Refresher **

2.0 hours **

Spare Parts Analysis **

1.0 hours **

Vacuum Bottle Integrity Check **

3.0 hours **

Final Report

3.0 hours

Note: ** indicates that the time may not be required depending on the
nature of the maintenance and the condition of the drive system. These
times are only estimations.

Annual Maintenance
(cont.)