D-10
Preventative Maintenance Schedule
7000A-RM001A-EN-P – January 2011
7000 “A” Frame
Rockwell Automation PowerFlex 7000 Preventative Maintenance Service Schedule
(cont.)
Interval
Period
(in
years)
11 12 13 14 15 16 17 18 19 20
Commissioning Activities
Door Mounted Air Filters
C/R C/R C/R C/R C/R C/R C/R C/R C/R C/R
Main
Cooling
Fan
Motor
I I I
RFB/R
I I I I I I
Redundant
Cooling
Fan
Motor
(if
supplied) I I I
RFB/R
I I I I I I
Air-Cooling
System
Small Aux. Cooling Fans “Caravel”
I
I
I
I
R
I
I
I
I
R
Mesh Filters
C C C C C C C C C C
De-ionizing Filter Cartridge
R R R R R R R R R R
All
Fittings/Connections/Hose
Clamps I I I I I I I I I I
Redundant
Cooling
Pump
Motors/Pumps I I I I I I I I I I
Redundant
Cooling
Pump
Motor
Seals I I I I I I I I I R
Liquid-Cooling
System
Thermostatic
Valve
Element
I I I R I I I I I I
Power
Devices
(SGCTs/SCRs)
I R I I I I I I I I
Snubber
Resistors/Sharing
Resistors/HECS
I I I I I I I I I I
Rectifier Snubber Capacitors
I
I
I
I
I
I I I I
Rv/R
Inverter
Snubber
Capacitors
I I I I I I I I I R
Power Switching
Components
Integrated Gate Driver Power Supply
I
I
I
I
RFB/R
I
I
I
I
RFB/R
Isolation
Transformer/Line
Reactor
I I I I M I I I I M
DC Link/Common Mode Choke
I
I
I
I
M
I
I
I
I
M
Integral
Magnetics/Power
Filters
Line/Motor
Filter
Capacitors
I I I I M I I I I M
AC/DC and DC/DC Power Supplies
I
I
I
I
RFB/R
I
I
I
I
RFB/R
Control
Boards
I I I I I I I I I I
Batteries (DCBs and CIB)
I
R
I
I
R
I
I
R
I
I
Control Cabinet
Components
Batteries (UPS)
I I I I R I I I I R
Low Voltage Terminal Connections/
Plug-in Connections
I I I I I I I I I I
Medium
Voltage
Connections
I I I I I I I I I I
Heatsink
Bolted
Connections
I I I I I I I I I I
Medium Voltage Connections (Rectifier)
–
I
–
–
–
I
–
–
–
I
Connections
Medium Voltage Connections (Inverter)
– – – – – – – – – I
Firmware
– Rv – – Rv – – Rv – –
Enhancements
Hardware
– Rv – – Rv – – Rv – –
Parameters
I Rv I I Rv I I Rv I I
Variables
I Rv I I Rv I I Rv I I
Operational
Conditions
Application
Concerns
I Rv I I Rv I I Rv I I
Spare Parts
Inventory/Needs
I Rv i I Rv I I Rv I I
Only applies to air-cooled VFDs (i.e. ‘A’ Frame and ‘B’ Frame)
If filter supplied is not a washable type, replace filter. If filter supplied is a washable type, wash or replace (depending on state of filter).
Only applies to liquid-cooled VFDs (i.e. ‘C’ Frame)
A 4-year replacement interval applies to 6-pulse or 18-pulse versions. Active Front End rectifiers have a 10-year rectifier snubber capacitor replacement interval.
Replace UPS batteries yearly for 50°C rated VFDs.
When rectifier snubber capacitors are replaced, the MV connections for rectifier need to be inspected.
When inverter snubber capacitors are replaced, the MV connections for inverter need to be inspected.
These components may be serviced while the VFD is running.