Replacement procedure for dc/dc power supply – Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive - Air-Cooled (A Frame) User Manual
Page 314
5-72
Component Definition and Maintenance
7000A-RM001A-EN-P – January 2011
7000 “A” Frame
Terminal/connections descriptions (cont.)
P3 – ISOLATOR
(To Isolator Modules)
PIN NO.
LABEL
DESCRIPTION ONLY
1
ISOLATOR
(+24V,1A)
+24V,1A/com4
2
ISOL_COMM
(com4)
0V/com4
3
EARTH EARTH
P4 – PWR
(To ACB)
PIN NO.
LABEL
DESCRIPTION ONLY
1
+24V_XIO
(+24V,2A)
+24V,2A/com3
2
XIO_COMM
(com3)
0V/com3
3
+HECSPWR
(+24V,1A)
+24V,1A/com2
4
LCOMM
(com2)
0V/com2
5
–HECSPWR
(-24V,1A)
-24V,1A/com2
6
+15V_PWR
(+15V,1A)
+15V,1A/com1
7
ACOMM
(com1)
0V/com1
8
–15V_PWR
(-15V,1A)
-15V,1A/com1
9
+5V_PWR
(+5V,5A)
+5V,10A/com1
10
DGND
(com1)
0V/com1
11
EARTH earth
ground
Replacement Procedure for DC/DC Power Supply
(Refer to Figure 5.57)
1. With the drive energized, check that all output voltages are present.
(View 1)
2. De-energize the drive, isolate and lock out the control power, and
remove all wire connections from the unit. (View 1)
3. Remove quantity of (4) M6 (H.H.T.R.S.) that will allow the DC/DC
Power Supply Assembly to be removed from the Low Voltage Panel.
(View 1)
4. Remove quantity of (4) M4 (P.H.M.S.) and Nylon Shoulder
Washers from the back of the Mounting Plate. ( View 2)
5. Replace old DC/DC Power Supply with the new one.
NOTE: Make sure the Black Insulation is between the DC/DC
Power Supply and the Mounting Plate. Repeat Steps 4, 3, 2, 1
in this order to replace unit. (View 2)
6. Ensure the ground wire of P4 plug is connected to the ground by M10
bolt
DC/DC Power Supply
(cont.)