Description
Specifications
Power Rating (Air Cooled)
200 to 1250 hp (150 to 933 kW)
Motor Type
Induction or Synchronous
Input Voltage Rating
2400V, 3300V, 4160V, 6600V
Input Voltage Tolerance
± 10% of Nominal
Voltage Sag -30%
Control Power Loss Ride-Through
5 Cycles (Std)
Input Protection
Surge Arrestors
Input Frequency
50/60 Hz, +/- 5%
Power Bus Short-circuit Current Withstand
5 Cycle
3300 V – 6000 V
25 kA RMS SYM
Basic Impulse Level
50 kV (0 – 1000 m)
Power Bus Design
Copper – Tin plated
Ground Bus
Copper – Tin plated 6 x 51 mm (¼ x 2 in.)
Customer Control Wire Way
Separate and Isolated
Input Power Circuit Protection
Vacuum Contactor with Fused Isolating Switch
(optional)
Input Impedance Device
Isolation Transformer or AC Line Reactor
Output Voltage
0 – 2300 V
0 – 3300 V
0 – 4000 V
0 – 6000 or 6300 V
Inverter Design
PWM
Inverter Switch
Symmetrical Gate Commutated Thyristor (SGCT)
Inverter Switch Failure Mode
Non-rupture, Non-arc
Inverter Switch Failure Rate (FIT)
100 per 1 Billion Hours Operation
Inverter Switch Cooling
Double Sided, Low Thermal Stress
Inverter Switching Frequency
420-540 Hz
Voltage
SGCTs (per phase)
Number of Inverter SGCTs
2400 V
3300 V
4160 V
6600 V
2
4
4
6
Voltage
PIV
SGCT PIV Rating
(Peak Inverse Voltage)
2400 V
3300 V
4160 V
6600 V
6500 V
6500 V
6500 V
6500 V
Rectifier Designs
AFE (Active Front End)
Rectifier Switch
SGCT
Rectifier Switch Failure Mode
Non-rupture, Non-arc
Rectifier Switch Failure Rate (FIT)
100 (SGCT) per 1 Billion Hours Operation
Rectifier Switch Cooling
Double Sided, Low Thermal Stress
Voltage Sag tolerance is reduced to -25% when control power is supplied from medium voltage via CPT.
Short-circuit fault rating based on input protection device (contactor or circuit breaker).
BIL rating based on altitudes < 1000 m (3,300 ft.) Refer to factory for derating on altitudes >1000 m).