Publication 2098-RM001C-EN-P – August 2002
Programming Reference
2-47
7
Set
I/O Receive
Select
USINT
1
Selects the output (consumed) assembly that is
updated when a Polled, Change-of-State, or Cyclic
I/O Message is received by the drive. If the value is
modified, you have to either close any existing I/O
Messaging connection(s), power cycle the drive,
reset the drive, or remove and reapply DeviceNet
power for the drive to use the modified value. Refer
to the Assembly Object for information on the data
format.
0 - No Data Consumed (default)
1 - Assembly Instance 1
2 - Assembly Instance 2
3 - Assembly Instance 3
4 - Assembly Instance 4
5 - Assembly Instance 5
6 - Assembly Instance 6
7 - Assembly Instance 7
8 - Assembly Instance 8
9 - Assembly Instance 9
8
Set
Poll Transmit
(Xmit) Select
USINT
1
Selects the input (produced) assembly that is
transmitted by the drive over a Polled I/O Messaging
connection. If the value is modified, you have to
either close any existing I/O Messaging
connection(s), power cycle the drive, reset the drive,
or remove and reapply DeviceNet power for the drive
to use the modified value. Refer to the Assembly
Object for information on the data format.
0 - Assembly Instance 10 (default)
1 - Assembly Instance 11
2 - Assembly Instance 12
3 - Assembly Instance 13
4 - Assembly Instance 14
5 - Assembly Instance 15
6 - Assembly Instance 16
7 - Assembly Instance 17
8 - Assembly Instance 18
9
Set
COS/Cyclic
Transmit (Xmit)
Select
USINT
1
Selects the response (produced) assembly that is
transmitted by the drive over a Change-of-State, or
Cyclic I/O Messaging connection. If the value is
modified, you have to either close any existing I/O
Messaging connection(s), power cycle the drive,
reset the drive, or remove and reapply DeviceNet
power for the drive to use the modified value. Refer
to the Assembly Object for information on the data
format.
0 - Assembly Instance 10 (default)
1 - Assembly Instance 13
2 - Assembly Instance 15
Parameter Object,
Instances ID = 1- 996
Parameter
Instance
Access
Rule
Parameter
Name
Data
Type
Data Size
(Bytes)
Units /
Scale
Description