Publication 2098-RM001C-EN-P – August 2002
2-88
Programming Reference
334
Set
Preset Position 7
Accel
UDINT
4
Cnts /
Sec
2
The acceleration rate used to change to a higher
velocity during a Preset Position 7 move.
Range: 0 to 0x7fffffff
Default: 100000
335
Set
Preset Position 7
Decel
UDINT
4
Cnts /
Sec
2
The deceleration rate used to change to a lower
velocity during a Preset Position 7 move.
Range: 0 to 0x7fffffff
Default: 100000
336
Set
Homing Type
USINT
1
Selects the type of homing operation the drive will
perform when the homing procedure is started.
0 - Home to Sensor, Forward to Marker (default)
1 - Home to Marker
2 - Home to Sensor
3 - Home to Sensor, Backward to Marker
4 - Home to Current Setting
5 - Home to Current Setting, Backward to Marker
337
Set
Auto-Start Home
USINT
1
Determines if the drive will begin the homing
procedure automatically when the drive is enabled.
0 - Auto-start homing inactive (default)
1 - Auto-start homing active only if not homed
2 - Auto-start homing always active
338
Set
Home Sensor
Backoff
USINT
1
Causes the drive to move in the direction opposite
the direction specified by the Homing Velocity
setting, when the homing procedure is started with
the Sensor input active. Motion will continue in the
reverse direction (moving at the Homing Accel,
Homing Decel, and Homing Velocity settings), until
the Sensor input is detected inactive, at which point
the normal homing procedure will take over.
Controls whether the drive backs off the sensor if
the sensor is active at the start of the homing
operation.
Note: This parameter does not apply if 'Home to
Marker' is selected as the Homing Type.
0 - Disable (default)
1 - Enable
339
Set
Homing Velocity
DINT
4
Cnts /
Sec
The commanded velocity used during homing. The
sign of the parameter value specifies the direction of
motion during homing.
Range: -0x7fffffff to 0x7fffffff
Default: 100000
340
Set
Homing Accel/
Decel
UDINT
4
Cnts /
Sec
2
The acceleration and deceleration rate used during
homing.
Range: 0 to 0x7fffffff
Default: 100000
341
Set
Home Offset
Move
DINT
4
Cnts
The distance the motor position will be from the
home position after the homing procedure is
complete.
Range: -0x7fffffff to 0x7fffffff
Default: 0
Parameter Object,
Instances ID = 1- 996
Parameter
Instance
Access
Rule
Parameter
Name
Data
Type
Data Size
(Bytes)
Units /
Scale
Description