Chapter 2

2Ć4

Selection Procedure (Part A)

Begin with digital board features using Table 2.B.

1. The hard fault response of the module is selected first. A hard fault

occurs when a module failure is detected in the event of a failure, the
analog output will either maintain the last value or will be set to the
minimum or maximum value. A single choice is made for both
outputs as to whether they hold last value or go to
minimum/maximum.

Select hold last value or go to minimum/maximum for the hard fault
response. Record your selection on Table 2.B by circling RIGHT for hold
last value or LEFT for minimum/maximum.

NOTE: If hold last value is selected for hard fault, output 1 and output 2
must still be selected for minimum or maximum. The selection
determines the state of outputs at module power-up (green LED flashing)
until the load/enter sequence is complete, or power-down of +5V dc. See
Table 2.C.

Table 2.B

Programming Plug Selections: Digital (leftĆhand) Board

Location

Function

Position

E1

Factory Configured

OUT

E2 [1]

Hard fault response:

Hold last value

Minimum/maximum value

RIGHT

LEFT

E3 through E9

Factory Configured

See figure 22

E10

Source of +5V dc

Backplane

External supply

IN

OUT

[1] The selection for E2 affects both outputs the same. The choice of minimum value or maximum

value for the hard fault output must be made on the analog board regardless of the choice of

E2. (see text and analog board plugs E4 and/or E5).