5 - calibration, General, Test equipment – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual
Page 136: Calibration

Chapter
5
5Ć1
Calibration
The PID module is calibrated before it leaves the factory. The calibration
of the module should be checked yearly. It can be returned to
Allen-Bradley Systems Division for factory calibration. Revision B and
later models can be calibrated using the procedures described in this
chapter.
The following test equipment and parts should be available. Some of this
equipment can be borrowed from the system installation or an
independent test station can be used.
DC Voltage Standard
+10V, 0.1mV resolution
Fluke 342A, or equivalent
Digital Voltmeter
5 1/2 digit, 0.01% accuracy
Keithly 191, Fluke 8300A, or
equivalent
Precision Resistor
AllenĆBradley Systems Division
250 ohms +0.02% 1/4 watt
PN 610996Ć01
Resistor
1000 ohms +l% watt
numerous sources
Industrial Terminal
AllenĆBradley system terminal or
spare, compatible with test PC.
Programmable Controller
System PC or space
Analog Power Supply
AllenĆBradley Power Supply (cat.
no. 1770ĆP1) +15V dc, Ć15V dc,
system supply or spare
Chassis Power Supply
AllenĆBradley (cat. no. 1771ĆP2)
system supply or spare
I/O Chassis
AllenĆBradley (cat. no. 1771ĆA1,ĆA2
or ĆA4) system chassis or system
spare
Extender Board
AllenĆBradley (cat. no. 1771ĆEX)
Field Wiring Arm
AllenĆBradley (cat. no. 1771ĆWF)
system spare
Alignment Tool
pottweeker"
Newark Electronic PN 35F616 or TV
duplex Aligner with plastic shaft, or
equivalent
General
Test Equipment